View larger
IN32N4-08F 124116 EATON ELECTRIC Break switch, 4P, 800A, fixed
IN32N4-08F
124116
EATON - MOELLER
1 Pcs.
Connectors > Switch disconnector
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for heavy electrical systems, this Eaton Moeller break switch (part number IN32N4-08F) handles the manual interruption of high electrical currents in commercial and industrial applications. Units of this type are routinely integrated into primary power distribution architectures to ensure safe load management and circuit isolation. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated current = rated uninterrupted current: I n = I u
- Making capacity Icm to 440 V 50/60 Hz: I cm
- t = 1 s: I cw
- t = 3 s: I cw
- Storage: ϑ
- Rated uninterrupted current at 50 °C: I u
- Rated uninterrupted current at 60 °C: I u
- Rated uninterrupted current at 70 °C: I u
- Rated impulse withstand voltage: U imp
- Rated operational voltage: U e
- Use in IT electrical power networks up to U = 440 V: I IT
- Rated insulation voltage: U i
- Switching capacity Rated short-circuit making capacity: I cm
- up to 440 V 50/60 Hz: I cm
- up to 690 V 50/60 Hz: I cm
More info
▲Product range | Air circuit-breakers/switch-disconnectors | ||
Product range | Open switch-disconnectors | ||
Current Range | over 4000 A | ||
Protective function | Switch disconnector | ||
Installation type | Fixed | ||
Construction size | IN32 | ||
Release system | Electronic release | ||
Standard/Approval | IEC | ||
Number of poles | 4 pole | ||
Degree of Protection | IP20, IP55 with protective cover | ||
Rated current = rated uninterrupted current | In= Iu | A | 800 |
Making capacity Icm to 440 V 50/60 Hz | Icm | kA | 55 |
t = 1 s | Icw | kA | 85 |
t = 3 s | Icw | kA | 65 |
| Notes Including rear connection main terminals and secondary terminal blocks according to ordered breaker options. | |||
| General | |||
Standards | IEC/EN 60947 | ||
Ambient temperature | |||
Storage | ϑ | °C | -40 - +70 |
Operating (open) | °C | -25 - +70 | |
Mounting position | >> | ||
Utilization category | B | ||
Degree of Protection | IP20, IP55 with protective cover | ||
Direction of incoming supply | as required | ||
| Main conducting paths | |||
Rated current = rated uninterrupted current | In= Iu | A | 800 |
Rated uninterrupted current at 50 °C | Iu | A | 800 |
Rated uninterrupted current at 60 °C | Iu | A | 800 |
Rated uninterrupted current at 70 °C | Iu | A | 800 |
Rated impulse withstand voltage | Uimp | V AC | 8000 |
Rated operational voltage | Ue | V AC | 690 |
Use in IT electrical power networks up to U = 440 V | IIT | kA | 13 |
Overvoltage category/pollution degree | III/3 | ||
Rated insulation voltage | Ui | V | 1000 |
| Switching capacity | |||
Rated short-circuit making capacity | Icm | ||
up to 440 V 50/60 Hz | Icm | kA | 55 |
up to 690 V 50/60 Hz | Icm | kA | 187 |
Rated short-time withstand current 50/60 Hz | |||
t = 1 s | Icw | kA | 85 |
t = 3 s | Icw | kA | 65 |
Operating times | |||
Closing delay via spring release | ms | 35 | |
Break times | ms | 40 | |
Total opening delay via shunt release | ms | 30 | |
Total opening delay via undervoltage release | ms | 35/70 | |
Maximum operating frequency | Ops./h | ||
Maximum operating frequency | Operations/h | 60 | |
Heat dissipation at rated current In | |||
Fixed mounting | W | 35 | |
Withdrawable units (switch with cassette) | W | 70 | |
| Weight | |||
Fixed mounting | |||
3-pole | kg | 68 | |
4-pole | kg | 86 | |
Withdrawable | |||
3-pole | kg | 80 | |
4-pole | kg | 102 | |
Cassette | |||
3 pole | kg | 34 | |
4 pole | kg | 38 | |
| Terminal capacities | |||
Copper bar | |||
Fixed mounting | |||
Black | mm | 2 x 5 x 50 | |
Withdrawable units | |||
Black | mm | 2 x 5 x 50 | |
| Permissible continuous current for circuit‐breakers operating in switchboards at various internal ambient temperatures. The switchboard’s internal ambient temperature should be estimated using the calculation methods of IEC regulation. | |||