Request QuoteProduct Overview
The N1-4-63 266002 Y7-266002 EATON ELECTRIC Switch-disconnector 4p 63A BG1 from Eaton Moeller is a four-pole switching device utilized in commercial and industrial electrical panels to safely disconnect supply lines. Multi-pole disconnects ensure complete separation of phase and neutral conductors during routine servicing or emergency interruptions.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Version as main switch (EF006981): Yes
- Version as maintenance-/service switch (EF006986): Yes
- Version as safety switch (EF006985): No
- Version as emergency stop installation (EF006959): Yes
- Version as reversing switch (EF009408): No
- Number of switches (EF005586): 1
- Max. rated operation voltage Ue AC (EF007355): 690 V
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 63 A
- Rated permanent current at AC-23, 400 V (EF011777): 0 A
- Rated permanent current at AC-21, 400 V (EF009165): 0 A
- Rated operation power at AC-3, 400 V (EF001364): 0 kW
- Rated short-time withstand current lcw (EF007050): 2 kA
- Rated operation power at AC-23, 400 V (EF007027): 30 kW
- Switching power at 400 V (EF009166): 0 kW
- Conditioned rated short-circuit current Iq (EF001444): 0 kA
More info
▲General specifications
IEC
Product specifications
Version as maintenance-/service switch
Version as emergency stop installation
Distribution board installation
Ground mounting
Intermediate mounting
Built-in device fixed built-in technique
Damp heat, constant, to IEC 60068-2-78
500 V AC (between auxiliary contacts and main contacts)
Other
160 A (415 V AC-22/23A, making and breaking capacity)
IP40 (with insulating surround)
IP66 (with door coupling rotary handle)
IP10 (tunnel terminal)
Min. 2 segments of 9 mm x 0.8 mm at box terminal
10000 operations at 400 V AC-1
7500 operations at 690 V AC-1
1000 operations at 400 V AC-23A
1000 operations at 415 V AC-23A
1000 operations at 690 V AC-23A
Disconnectors/main switches
Interlockable
100 kA at 400/415 V
63 gG/gL
10 kA at 690 V
63 gG/gL
M6 at rear-side screw connection
Max. 16 mm x 5 mm direct at switch rear-side connection
6 mm² - 16 mm² (2x) at box terminal
16 mm² (1x) at tunnel terminal
10 mm² - 16 mm² (1x) at box terminal
6 mm² - 16 mm² (2x) direct at switch rear-side connection
16 mm² (1x) at tunnel terminal
10 mm² - 16 mm² (2x) direct at switch rear-side connection
6 mm² - 25 mm² (2x) at box terminal
10 mm² - 70 mm² (1x) at box terminal
25 mm² (2x) direct at switch rear-side connection
25 mm² - 95 mm² (1x) at 1-hole tunnel terminal
25 mm² - 70 mm² (1x) direct at switch rear-side connection