View larger
DMV-1000N/4 1814447 Y8-1814447 EATON ELECTRIC Switch-disconnector, 4 pole, 1000 A, Without rotary handle and..
DMV-1000N/4
1814447
Y8-1814447
EATON - MOELLER
1 Pcs.
Connectors > Switch disconnector
DUMECO Switch-Disconnectors
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A DMV-1000N/4 1814447 Y8-1814447 EATON ELECTRIC Switch-disconnector is a high-capacity electrical interrupting device used to safely break heavy load currents and isolate high-voltage power distribution networks. These industrial disconnectors protect downstream infrastructure by providing visible, reliable circuit separation under load. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Version as main switch (EF006981): Yes
- Version as maintenance-/service switch (EF006986): Yes
- Version as safety switch (EF006985): No
- Version as emergency stop installation (EF006959): Yes
- Version as reversing switch (EF009408): No
- Number of switches (EF005586): 1
- Max. rated operation voltage Ue AC (EF007355): 690 V
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 1000 A
- Rated permanent current at AC-23, 400 V (EF011777): 759 A
- Rated permanent current at AC-21, 400 V (EF009165): 1000 A
- Rated operation power at AC-3, 400 V (EF001364): 0 kW
- Rated operation power at AC-23, 400 V (EF007027): 425 kW
- Switching power at 400 V (EF009166): 375 kW
- Conditioned rated short-circuit current Iq (EF001444): 100 kA
More info
▲General specifications
CE
Lloyds
VDE 0660
IEC/EN 60947-3
RoHS
IEC/EN 60947
IEC/EN 60204
KEMA
Features & Functions
Version as maintenance-/service switch
Version as main switch
General
- Main switch
- Switch-disconnector
Distribution board installation
Climatic environmental conditions
Terminal capacities
Electrical rating
Short-circuit rating
65 kA (at In = 630)
Max. 4200 kA²s (at In = 1000)
50 kA at In = 1000
36 kA, Contacts, 1 second