View larger
Images are for illustrative purposes only. Please refer to data sheet for details
DCM-40/1-SK 1314105 Y8-1314105 EATON ELECTRIC Switch-disconnector, 3 pole + N, 40 A, Without rotary handle a..
DCM-40/1-SK
1314105
Y8-1314105
EATON - MOELLER
1 Pcs.
Switch-disconnector, 3 pole + N, 40 A, Without rotary handle and drive shaft, surface mounting, Vertical connection
DCM-40/1-SK
Eaton DCM Switch-disconnector, DCM, 40 A, 3P + N (solid), Stop Function optional, Without rotary handle and drive shaft, Vertical connection
Switch-disconnector, Product range: Switch-disconnector, Main switch, maintenance switch, Part group reference: DCM, Stop Function: optional, Without rotary handle and drive shaft, 3 pole + SN (direct), Degree of Protection: IP20, Design: surface mounting, Motor rating AC-23A, 50 - 60 Hz 400 V: P = 20 kW, Rated uninterrupted current: Iu = 40 A, Connection technique: Vertical connection, Standards: IEC/EN 60947, VDE 0660, IEC/EN 60204, Switch-disconnector according to IEC/EN 60947-3
Connectors > Switch disconnector
DUMECO Switch-Disconnectors
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Switch-disconnector units like the Eaton Moeller DCM-40/1-SK are installed in distribution boards to safely disconnect power loads during maintenance procedures. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Version as main switch (EF006981): No
- Version as maintenance-/service switch (EF006986): No
- Version as safety switch (EF006985): No
- Version as emergency stop installation (EF006959): No
- Version as reversing switch (EF009408): No
- Number of switches (EF005586): 1
- Max. rated operation voltage Ue AC (EF007355): 415 V
- Rated operating voltage (EF001435): 415 V
- Rated permanent current Iu (EF001389): 40 A
- Rated permanent current at AC-23, 400 V (EF011777): 40 A
- Rated permanent current at AC-21, 400 V (EF009165): 40 A
- Rated operation power at AC-3, 400 V (EF001364): 0 kW
- Rated short-time withstand current lcw (EF007050): 1 kA
- Rated operation power at AC-23, 400 V (EF007027): 20 kW
- Switching power at 400 V (EF009166): 20 kW
- Conditioned rated short-circuit current Iq (EF001444): 50 kA
More info
▲General specifications
Product Name
Eaton DCM Switch-disconnector
Catalog Number
1314105
Model Code
DCM-40/1-SK
EAN
8711426803848
Product Length/Depth
150 mm
Product Height
80 mm
Product Width
90 mm
Product Weight
0.4 kg
Certifications
RoHS
EAC
IEC/EN 60204
IEC/EN 60947
IEC/EN 60947-3
KEMA
VDE 0660
Lloyds
CE
EAC
IEC/EN 60204
IEC/EN 60947
IEC/EN 60947-3
KEMA
VDE 0660
Lloyds
CE
Features & Functions
Functions
Optional Stop Function
Number of poles
Three-pole + N
General
Actuator color
Other
Actuator type
Other
Connection type
Vertical
Degree of protection
NEMA Other
Degree of protection (front side)
IP20
Lifespan, mechanical
10,000 Operations
Mounting method
Surface mounting
Mounting position
As required
Overvoltage category
III
Pollution degree
3
Product Category
Rated impulse withstand voltage (Uimp)
6000 V
Safety parameter (EN ISO 13849-1)
B10d values as per EN ISO 13849-1, table C.1
Suitable for
Ground mounting
Distribution board installation
Distribution board installation
Climatic environmental conditions
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Ambient storage temperature - min
-30 °C
Ambient storage temperature - max
80 °C
Terminal capacities
Terminal capacity
2.5 - 16 mm², solid
1.5 - 25 mm², flexible
1.5 - 25 mm², flexible
Stripping length (main cable)
14 mm
Electrical rating
Rated breaking capacity at 400/415 V (cos phi to IEC 60947-3)
320 A
Rated insulation voltage (Ui)
690 V
Rated operational current (Ie) at AC-21, 400 V, 415 V
40 A
Rated operational current (Ie) at AC-22, 380 V, 400 V, 415 V
40 A
Rated operational current (Ie) at AC-23A, 400 V, 415 V
40 A
Rated operational power at AC-23A, 400 V, 50 Hz
20 kW
Rated operational power at AC-3, 380/400 V, 50 Hz
0 kW
Rated operational voltage (Ue) at AC - max
415 V
Rated uninterrupted current (Iu)
40 A
Uninterrupted current
Rated uninterrupted current Iu is specified for max. cross-section.
Short-circuit rating
Breaking current
7 kA
Let-through energy
Max. 12 kA²s
Rated conditional short-circuit current (Iq)
50 kA
Rated short-circuit making capacity (Icm)
2.2 kAeff
Rated short-time withstand current (Icw)
1 kA
1 kA, Contacts, 1 second
1 kA, Contacts, 1 second
Short-circuit protection rating
50, Fuse, Contacts
Contacts
Number of auxiliary contacts (change-over contacts)
0
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
0
Design verification
Equipment heat dissipation, current-dependent Pvid
0.6 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
3 W
Rated operational current for specified heat dissipation (In)
40 A
Static heat dissipation, non-current-dependent Pvs
0 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.