View larger
N3-630-AVE 110769 Y7-110769 EATON ELECTRIC Switch-disconnector 3p 630A + withdrawable unit
N3-630-AVE
110769
Y7-110769
EATON - MOELLER
1 Pcs.
Connectors > Switch disconnector
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for heavy electrical distribution networks, the Eaton Moeller N3-630-AVE switch-disconnector safely interrupts high-capacity circuits under load conditions.
Heavy-duty disconnectors like this one are commonly installed in main switchboards and industrial power centers to provide visible, reliable isolation for entire electrical systems or large branch circuits.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Version as main switch (EF006981): Yes
- Version as maintenance-/service switch (EF006986): Yes
- Version as safety switch (EF006985): No
- Version as emergency stop installation (EF006959): Yes
- Version as reversing switch (EF009408): No
- Number of switches (EF005586): 1
- Max. rated operation voltage Ue AC (EF007355): 690 V
- Rated operating voltage (EF001435): 690 V
- Rated permanent current at AC-23, 400 V (EF011777): 0 A
- Rated permanent current at AC-21, 400 V (EF009165): 0 A
- Rated operation power at AC-3, 400 V (EF001364): 0 kW
- Rated short-time withstand current lcw (EF007050): 12 kA
- Rated operation power at AC-23, 400 V (EF007027): 315 kW
- Switching power at 400 V (EF009166): 0 kW
- Conditioned rated short-circuit current Iq (EF001444): 0 kA
- Number of poles (EF001391): 3
More info
▲General specifications
IEC
Product specifications
Version as main switch
Motor drive optional
Version as maintenance-/service switch
Distribution board installation
Intermediate mounting
Ground mounting
Built-in device slide-in technique (withdrawable)
Damp heat, constant, to IEC 60068-2-78
300 V AC (between the auxiliary contacts)
Other
500 A (415 V AC-23A, making and breaking capacity)
630 A (690 V AC-22A, making and breaking capacity)
500 A (690 V AC-23A, making and breaking capacity)
IP40 (with insulating surround)
IP66 (with door coupling rotary handle)
IP10 (tunnel terminal)
Max. 8 segments of 24 mm x 1 mm (2x) at box terminal
Min. 6 segments of 16 mm x 0.8 mm at box terminal
Min. 6 segments of 16 mm x 0.8 mm at rear-side connection (punched)
10 segments of 50 mm x 1 mm (2x) at rear-side width extension
Max. 10 segments of 24 mm x 1 mm + 5 segments of 24 mm x 1 mm
3000 operations at 690 V AC-1
3000 operations at 400 V AC-3
2000 operations at 690 V AC-3
3000 operations at 400 V AC-1
3000 operations at 415 V AC-1
Disconnectors/main switches
Interlockable
80 kA at 690 V
100 kA at 400/415 V
80 kA at 690 V
100 kA at 400/415 V
Max. 10 mm x 50 mm (2x) at rear-side width extension
Min. 20 mm x 5 mm direct at switch rear-side connection
300 mm² (2x) at rear-side width extension
16 mm² (2x) at box terminal
16 mm² (2x) direct at switch rear-side connection
16 mm² (1x) direct at switch rear-side connection
10 mm² - 16 mm² (2x) direct at switch rear-side connection
25 mm² - 120 mm² (1x) direct at switch rear-side connection
25 mm² - 185 mm² (1x) at 1-hole tunnel terminal
50 mm² - 240 mm² (1x) at 2-hole tunnel terminal
50 mm² - 240 mm² (2x) at 2-hole tunnel terminal
25 mm² - 120 mm² (2x) at box terminal
25 mm² - 120 mm² (2x) direct at switch rear-side connection