View larger
IN63N3-40F 124316 EATON ELECTRIC Switch-disconnector, 3p, 4000A, fixed
IN63N3-40F
124316
EATON - MOELLER
1 Pcs.
Connectors > Switch disconnector
Circuit Breakers IZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller IN63N3-40F 124316 EATON ELECTRIC Switch-disconnector, 3p, 4000A, fixed is a heavy-duty mechanical switching device used to safely isolate electrical circuits and distribution systems from power sources during maintenance. These components provide a visible break in industrial networks to protect personnel and equipment.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated current = rated uninterrupted current: I n = I u
- Making capacity Icm to 440 V 50/60 Hz: I cm
- t = 1 s: I cw
- t = 3 s: I cw
- Storage: ϑ
- Rated uninterrupted current at 50 °C: I u
- Rated uninterrupted current at 60 °C: I u
- Rated uninterrupted current at 70 °C: I u
- Rated impulse withstand voltage: U imp
- Rated operational voltage: U e
- Use in IT electrical power networks up to U = 440 V: I IT
- Rated insulation voltage: U i
- Switching capacity Rated short-circuit making capacity: I cm
- up to 440 V 50/60 Hz: I cm
- up to 690 V 50/60 Hz: I cm
- t = 1 s: I cw
More info
▲Product range | Air circuit-breakers/switch-disconnectors | ||
Product range | Open switch-disconnectors | ||
Current Range | over 4000 A | ||
Protective function | Switch disconnector | ||
Installation type | Fixed | ||
Construction size | IN63 | ||
Release system | Electronic release | ||
Standard/Approval | IEC | ||
Number of poles | 3 pole | ||
Degree of Protection | IP20, IP55 with protective cover | ||
Rated current = rated uninterrupted current | In= Iu | A | 4000 |
Making capacity Icm to 440 V 50/60 Hz | Icm | kA | 138 |
t = 1 s | Icw | kA | 85 |
t = 3 s | Icw | kA | 65 |
| Notes Including rear connection main terminals and secondary terminal blocks according to ordered breaker options. | |||
| General | |||
Standards | IEC/EN 60947 | ||
Ambient temperature | |||
Storage | ϑ | °C | -40 - +70 |
Operating (open) | °C | -25 - +70 | |
Mounting position | >> | ||
Utilization category | B | ||
Degree of Protection | IP20, IP55 with protective cover | ||
Direction of incoming supply | as required | ||
| Main conducting paths | |||
Rated current = rated uninterrupted current | In= Iu | A | 4000 |
Rated uninterrupted current at 50 °C | Iu | A | 4000 |
Rated uninterrupted current at 60 °C | Iu | A | 4000 |
Rated uninterrupted current at 70 °C | Iu | A | 4000 |
Rated impulse withstand voltage | Uimp | V AC | 8000 |
Rated operational voltage | Ue | V AC | 690 |
Use in IT electrical power networks up to U = 440 V | IIT | kA | 88888888 |
Overvoltage category/pollution degree | III/3 | ||
Rated insulation voltage | Ui | V | 1000 |
| Switching capacity | |||
Rated short-circuit making capacity | Icm | ||
up to 440 V 50/60 Hz | Icm | kA | 138 |
up to 690 V 50/60 Hz | Icm | kA | 187 |
Rated short-time withstand current 50/60 Hz | |||
t = 1 s | Icw | kA | 85 |
t = 3 s | Icw | kA | 65 |
Operating times | |||
Closing delay via spring release | ms | 35 | |
Break times | ms | 40 | |
Total opening delay via shunt release | ms | 40 | |
Total opening delay via undervoltage release | ms | 35/70 | |
Maximum operating frequency | Ops./h | ||
Maximum operating frequency | Operations/h | 60 | |
Heat dissipation at rated current In | |||
Fixed mounting | W | 380 | |
Withdrawable units (switch with cassette) | W | 750 | |
| Weight | |||
Fixed mounting | |||
3-pole | kg | 108 | |
4-pole | kg | 145 | |
Withdrawable | |||
3-pole | kg | 139 | |
4-pole | kg | 166 | |
Cassette | |||
3 pole | kg | 103 | |
4 pole | kg | 103 | |
| Terminal capacities | |||
Copper bar | |||
Fixed mounting | |||
Black | mm | 4 x 10 x 100 | |
Withdrawable units | |||
Black | mm | 4 x 10 x 100 | |
| Permissible continuous current for circuit‐breakers operating in switchboards at various internal ambient temperatures. The switchboard’s internal ambient temperature should be estimated using the calculation methods of IEC regulation. | |||