View larger
PN2-200 266006 Y7-266006 EATON ELECTRIC Switch-disconnector 3p, 200A
PN2-200
266006
Y7-266006
EATON - MOELLER
1 Pcs.
Connectors > Switch disconnector
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
PN2-200 by Eaton Moeller functions as a switch-disconnector designed for safely interrupting load currents in heavy-duty commercial and industrial electrical distribution setups. Devices of this classification provide reliable electrical isolation for switchboards, motor control centers, and panelboards during routine service tasks.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Version as main switch (EF006981): Yes
- Version as maintenance-/service switch (EF006986): Yes
- Version as safety switch (EF006985): No
- Version as emergency stop installation (EF006959): Yes
- Version as reversing switch (EF009408): No
- Number of switches (EF005586): 1
- Max. rated operation voltage Ue AC (EF007355): 690 V
- Rated operating voltage (EF001435): 690 V
- Rated permanent current at AC-23, 400 V (EF011777): 0 A
- Rated permanent current at AC-21, 400 V (EF009165): 0 A
- Rated operation power at AC-3, 400 V (EF001364): 0 kW
- Rated short-time withstand current lcw (EF007050): 3.5 kA
- Rated operation power at AC-23, 400 V (EF007027): 110 kW
- Switching power at 400 V (EF009166): 0 kW
- Conditioned rated short-circuit current Iq (EF001444): 0 kA
- Number of poles (EF001391): 3
More info
▲General specifications
IEC
Product specifications
Version as maintenance-/service switch
Version as emergency stop installation
Distribution board installation
Ground mounting
Built-in device fixed built-in technique
Intermediate mounting
Damp heat, cyclic, to IEC 60068-2-30
500 V AC (between auxiliary contacts and main contacts)
Other
250 A (415 V AC-22/23A, making and breaking capacity)
IP20
IP66 (with door coupling rotary handle)
IP10 (tunnel terminal)
Max. 10 segments of 16 mm x 0.8 mm at box terminal
Min. 2 segments of 9 mm x 0.8 mm at box terminal
Max. 8 segments of 15.5 mm x 0.8 mm (2x) at box terminal
Min. 2 segements of 16 mm x 0.8 mm at rear-side connection (punched)
10000 operations at 415 V AC-1
5000 operations at 690 V AC-3
7500 operations at 690 V AC-1
7500 operations at 400 V AC-3
7500 operations at 415 V AC-3
Interlockable
80 kA at 690 V
100 kA at 400/415 V
80 kA at 690 V
PN2(N2)-160…250: 250 AgGgL
Max. 24 mm x 8 mm direct at switch rear-side connection
M8 at rear-side screw connection
16 mm² (1x) at tunnel terminal
10 mm² - 16 mm² (1x) direct at switch rear-side connection
10 mm² - 16 mm² (1x) at box terminal
6 mm² - 16 mm² (2x) at box terminal
16 mm² (1x) at tunnel terminal
10 mm² - 16 mm² (1x) direct at switch rear-side connection
25 mm² - 70 mm² (2x) at box terminal
25 mm² - 70 mm² (2x) direct at switch rear-side connection
25 mm² - 185 mm² (1x) at box terminal
25 mm² - 185 mm² (1x) at 1-hole tunnel terminal