View larger
PN2-160 266005 Y7-266005 EATON ELECTRIC Switch-disconnector 3p, 160A
PN2-160
266005
Y7-266005
EATON - MOELLER
1 Pcs.
Connectors > Switch disconnector
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The PN2-160 266005 Y7-266005 EATON ELECTRIC Switch-disconnector is a robust 3-pole unit built to safely interrupt load currents and provide dependable circuit isolation in industrial electrical systems. These devices are standard components in panel boards and distribution units, ensuring systems can be securely de-energized during upkeep. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Version as main switch (EF006981): Yes
- Version as maintenance-/service switch (EF006986): Yes
- Version as safety switch (EF006985): No
- Version as emergency stop installation (EF006959): Yes
- Version as reversing switch (EF009408): No
- Number of switches (EF005586): 1
- Max. rated operation voltage Ue AC (EF007355): 690 V
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 160 A
- Rated permanent current at AC-23, 400 V (EF011777): 0 A
- Rated permanent current at AC-21, 400 V (EF009165): 0 A
- Rated operation power at AC-3, 400 V (EF001364): 0 kW
- Rated short-time withstand current lcw (EF007050): 3.5 kA
- Rated operation power at AC-23, 400 V (EF007027): 90 kW
- Switching power at 400 V (EF009166): 0 kW
- Conditioned rated short-circuit current Iq (EF001444): 0 kA
More info
▲General specifications
IEC
Product specifications
Version as emergency stop installation
Version as main switch
Built-in device fixed built-in technique
Distribution board installation
Intermediate mounting
Ground mounting
Damp heat, constant, to IEC 60068-2-78
500 V AC (between auxiliary contacts and main contacts)
Other
160 A (690 V AC-22/23A, making and breaking capacity)
IP66 (with door coupling rotary handle)
IP40 (with insulating surround)
IP00 (terminations, phase isolator and band terminal)
Max. 8 segments of 15.5 mm x 0.8 mm (2x) at box terminal
Max. 10 segments of 16 mm x 0.8 mm at box terminal
Min. 2 segements of 16 mm x 0.8 mm at rear-side connection (punched)
Max. 10 segments of 24 mm x 0.8 mm at rear-side connection (punched)
10000 operations at 415 V AC-1
5000 operations at 690 V AC-3
10000 operations at 400 V AC-1
7500 operations at 400 V AC-3
7500 operations at 415 V AC-3
Disconnectors/main switches
PN2(N2)-160…250: 250 AgGgL
100 kA at 400/415 V
100 kA at 400/415 V
PN2(N2)-160…250: 250 AgGgL
M8 at rear-side screw connection
Max. 24 mm x 8 mm direct at switch rear-side connection
10 mm² - 16 mm² (1x) at box terminal
6 mm² - 16 mm² (2x) direct at switch rear-side connection
10 mm² - 16 mm² (1x) direct at switch rear-side connection
6 mm² - 16 mm² (2x) at box terminal
10 mm² - 16 mm² (2x) direct at switch rear-side connection
16 mm² (1x) at tunnel terminal
25 mm² - 185 mm² (1x) at box terminal
25 mm² - 70 mm² (2x) direct at switch rear-side connection
25 mm² - 185 mm² (1x) at 1-hole tunnel terminal
25 mm² - 185 mm² (1x) direct at switch rear-side connection