EATON - MOELLER IN20B3-16F IN20B3-16F 123427 EATON ELECTRIC Switch-disconnector, 3p, 1600A, fixed View larger
Images are for illustrative purposes only. Please refer to data sheet for details

IN20B3-16F 123427 EATON ELECTRIC Switch-disconnector, 3p, 1600A, fixed

IN20B3-16F

123427

EATON - MOELLER

1 Pcs.

Switch-disconnector, 3p, 1600A, fixed Switch-disconnector, Air circuit-breakers/switch-disconnectors, Open switch-disconnectors, 4000 to 6300 A, without protection, Fixed, Construction size: IN20, Standard/Approval: IEC, Number of poles: 3 pole, Degree of Protection: IP20, IP55 with protective cover, Rated current = rated uninterrupted current: In = Iu 1600 A, up to 440 V 50/60 Hz: Icm 55 kA, t = 1 s: Icw 50 kA

Connectors > Switch disconnector

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Handling massive electrical loads in industrial distribution frameworks requires a robust component like the Eaton Moeller IN20B3-16F switch-disconnector. Fixed high-capacity disconnectors protect infrastructure by providing reliable circuit interruption during high-fault scenarios. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Rated current = rated uninterrupted current: I n = I u
  • up to 440 V 50/60 Hz: I cm
  • t = 1 s: I cw
  • Storage: ϑ
  • Rated uninterrupted current at 50 °C: I u
  • Rated uninterrupted current at 60 °C: I u
  • Rated uninterrupted current at 70 °C: I u
  • Rated impulse withstand voltage: U imp
  • Rated operational voltage: U e
  • Use in IT electrical power networks up to U = 440 V: I IT
  • Rated insulation voltage: U i
  • Switching capacity Rated short-circuit making capacity: I cm
  • up to 440 V 50/60 Hz: I cm
  • up to 690 V 50/60 Hz: I cm
  • Maximum operating frequency: Operations/h
  • Version as main switch (EF006981): No

More info

▲
Delivery program
Product range
Air circuit-breakers/switch-disconnectors
Product range
Open switch-disconnectors
Current Range
4000 to 6300 A
Protective function
without protection
Installation type
Fixed
Construction size
IN20
Standard/Approval
IEC
Number of poles
3 pole
Degree of Protection
IP20, IP55 with protective cover
Rated current = rated uninterrupted current
In= Iu A 1600
up to 440 V 50/60 Hz
Icm kA 55
t = 1 s
Icw kA 50
Notes

Including rear connection main terminals and secondary terminal blocks according to ordered breaker options.

Technical data
General
Standards
IEC/EN 60947
Ambient temperature
Storage
ϑ °C -40 - +70
Operating (open)
°C -25 - +70
Mounting position
Utilization category
B
Degree of Protection
IP20, IP55 with protective cover
Direction of incoming supply
as required
Main conducting paths
Rated current = rated uninterrupted current
In= Iu A 1600
Rated uninterrupted current at 50 °C
Iu A 1600
Rated uninterrupted current at 60 °C
Iu A 1500
Rated uninterrupted current at 70 °C
Iu A 1350
Rated impulse withstand voltage
Uimp V AC 8000
Rated operational voltage
Ue V AC 690
Use in IT electrical power networks up to U = 440 V
IIT kA 23
Overvoltage category/pollution degree
III/3
Rated insulation voltage
Ui V 1000
Switching capacity
Rated short-circuit making capacity
Icm
up to 440 V 50/60 Hz
Icm kA 55
up to 690 V 50/60 Hz
Icm kA 105
Operating times
Closing delay via spring release
ms 35
Break times
ms 40
Total opening delay via shunt release
ms 30
Total opening delay via undervoltage release
ms 35/70
Maximum operating frequency
Ops./h
Maximum operating frequency
Operations/h 60
Heat dissipation at rated current In
Fixed mounting
W 240
Withdrawable units (switch with cassette)
W 420
Weight
Fixed mounting
3-pole
kg 43
4-pole
kg 54
Withdrawable
3-pole
kg 48
4-pole
kg 62
Cassette
3 pole
kg 34
4 pole
kg 38
Terminal capacities
Copper bar
Fixed mounting
Black
mm 2 x 5 x 100
Withdrawable units
Black
mm 2 x 5 x 100


Permissible continuous current for circuit‐breakers operating in switchboards at various internal ambient temperatures. The switchboard’s internal ambient temperature should be estimated using the calculation methods of IEC regulation.


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.