Product range | Service distribution board IVS | ||
Basic function | Wall-mounting distribution system | ||
Single unit/Complete unit | Complete housing | ||
Degree of Protection | IP30 (only with door) | ||
Description | Profi Plus basic enclosures Module design, can be dismantled completely Exchangeable door hinges | ||
Material | Sheet steel | ||
Surface finish | Polyester powder coating Phosphated RAL 9016, traffic white | ||
Colour | RAL 9016, traffic white | ||
Information about equipment supplied | including base frame, side panels, bottom/top panels and door Including support frame for the IVS mounting units including insulating surround and mounted insulated support bracket including cable entry at top, with push-through flange | ||
Width | mm | 830 | |
Height | mm | 1060 | |
Depth | mm | 262 |
| General | |||
Standards | EN 60439-1/3 IEC 62208 | ||
Protection class | 1 | ||
Degree of Protection | IP30 (only with door) | ||
Power loss | |||
Max. admissible heat dissipation, ambient air temperature +35 °C | W | 203 | |
Weight | kg | 39.8 | |
| Material characteristics | |||
Material | Sheet steel | ||
Surface treatment | Painting, phosphated and polyester powder coating | ||
Surface finish | Polyester powder coating Phosphated RAL 9016, traffic white | ||
Colour | RAL 9016, traffic white | ||
Material characteristics | |||
Type Door | Doors with covered hinges Can be removed from 90° | ||
door opening angle | 167° (single mounting) 60° (combination mounting) | ||
Door interlock | Hinge handle with three-point turn-lock Cylinder lock | ||
| Material properties | |||
Mechanical | |||
Impact resistance | IK07 | ||
Cable entry | Various covers allow cable entry from above and/or below | ||
Electrical | |||
Rated operational voltage | Ue | V | 690 |
Rated frequency | f | Hz | 50 |
Rated operational current | Ie | CSA | 630 |
Max. admissible heat dissipation, ambient air temperature +35 °C | W | 203 | |
Earthings | M5 earthing point screw (base frame) M5 self-tapping screw (enclosure side plate, top/bottom panel) M6 weld stud (door) | ||
Technical data for design verification | |||
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees, calculated as per IEC 60890 | |||
Individual enclosure for wall mounting | PV | CO | 100 |
Starting enclosure for wall mounting | PV | CO | 94 |
Middle enclosure for wall mounting | PV | CO | 90 |
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees, calculated as per IEC 60890 | |||
Individual enclosure for wall mounting | PV | CO | 201 |
Starting enclosure for wall mounting | PV | CO | 189 |
Middle enclosure for wall mounting | PV | CO | 181 |
IEC/EN 61439 design verification | |||
10.2 Strength of materials and parts | |||
10.2.2 Corrosion resistance | Meets the product standard's requirements. | ||
10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. | ||
10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. | ||
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects | Meets the product standard's requirements. | ||
10.2.4 Resistance to ultra-violet (UV) radiation | Not relevant to indoor installations. | ||
10.2.5 Lifting | Does not apply to enclosures without lifting aids. | ||
10.2.6 Mechanical impact | IK07 | ||
10.2.7 Inscriptions | Meets the product standard's requirements. | ||
10.3 Degree of protection of ASSEMBLIES | IP30 | ||
10.4 Clearances and creepage distances | Is the panel builder's responsibility. | ||
10.5 Protection against electric shock | < 0.1 Ω; meets the product standard's requirements. | ||
10.6 Incorporation of switching devices and components | Is the panel builder's responsibility. | ||
10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. | ||
10.8 Connections for external conductors | Is the panel builder's responsibility. | ||
10.9 Insulation properties | |||
10.9.2 Power-frequency electric strength | Ui= 440 V AC | ||
10.9.3 Impulse withstand voltage | 4 kV | ||
10.9.4 Testing of enclosures made of insulating material | Does not apply to metal enclosures. | ||
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. | ||
10.11 Short-circuit rating | Is the panel builder's responsibility. | ||
10.12 Electromagnetic compatibility | Is the panel builder's responsibility. | ||
10.13 Mechanical function | Meets the product standard's requirements. |
| Feature Name | Feature Value |
|---|---|
| Number of rows (EF000266) | 6 |
| Width in number of modular spacings (EF002950) | 36 |
| Type of covering (EF000339) | Door |
| Cover model (EF009212) | Closed |
| Transparent cover/door (EF006244) | No |
| Signal passing door (EF015941) | No |
| With lock (EF006306) | No |
| Housing material (EF001596) | Steel |
| Built-in depth (EF000218) | 0 mm |
| Inner depth (EF001131) | 257.5 mm |
| Earthing terminal block (EF015776) | No |
| Neutral terminal block (EF015777) | No |
| DIN-rail (EF001134) | No |
| With mounting plate (EF000118) | No |
| Extension possible (EF001088) | No |
| EMC-version (EF001062) | No |
| Colour (EF000007) | White |
| RAL-number (EF000116) | 9016 |
| Degree of protection (IP) (EF005474) | IP30 |
| Height (EF000040) | 1075 mm |
| Width (EF000008) | 830 mm |
| Depth (EF000049) | 280 mm |