EATON - MOELLER BP-MN-600/12/1,75 BP-MN-600/12/1,75 119200 0002460732 EATON ELECTRIC Standard-compliant "mask" distribution board, WxHxD 573 x.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

BP-MN-600/12/1,75 119200 0002460732 EATON ELECTRIC Standard-compliant "mask" distribution board, WxHxD 573 x..

BP-MN-600/12/1,75

119200

0002460732

EATON - MOELLER

1 Pcs.

Standard-compliant "mask" distribution board, WxHxD = 573 x 1200 x 175 mm Standard-compliant zmaskz distribution board, IP30, BP-MN-, width 573 mm, outside height 1200 mm, front plate height 1150 mm, depth 175 mm, with MSW assembly, but without BPZ-MES mounting subrack, top adjustment plate insert, welded distribution board

Automation > Enclosure/switchgear cabinet (empty)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton xEnergy Basic LV systems Low voltage switchgear
Catalog Number
119200
Model Code
BP-MN-600/12/1,75
EAN
4015081173372
Product Length/Depth
185 mm
Product Height
1210 mm
Product Width
585 mm
Product Weight
11 kg
Compliances
RoHS conform

Delivery program

Color
Gray

Technical data - mechanical

Surface finishing
Powder coating
Material
Steel
Material quality
Other
Number of connector holes
0
Number of covers/doors
0
Number of locks
0
Built-in depth
175 mm
Permissible load of the door(s) according to IEC 62208 - max
0 N
Permissible load of the enclosure according to IEC 62208 - max
0 N
Permissible load of the mounting plate according to IEC 62208 - max
0 N
Installation type
Floor installation possible

Temperature-rise verification as per IEC 60890

Heat diss. ambient 35°C delta T: 20°C wall mount middle encl. top (IEC 60890)
55 W
Heat diss. ambient 35°C delta T: 35°C wall mount middle encl. top (IEC 60890)
111 W
Heat diss. ambient 35°C delta T:20°C wall mount individ. encl. top (IEC 60890)
57 W
Heat diss. ambient 35°C delta T:20°C wall mount starting encl. top (IEC 60890)
74 W
Heat diss. ambient 35°C delta T:35°C wall mount individ. encl. top (IEC 60890)
115 W
Heat diss. ambient 35°C delta T:35°C wall mount starting encl. top (IEC 60890)
149 W
Thermal dissipation (Delta T = 20 K) according to IEC/TR 60890
0 W

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2.5 Lifting
Does not apply to enclosures without lifting aids.
10.2.6 Mechanical impact
IK07
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
IP30
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
< 0.1 Ω; meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Ui = 440 V AC
10.9.3 Impulse withstand voltage
4 kV
10.9.4 Testing of enclosures made of insulating material
Does not apply to metal enclosures.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility.
10.13 Mechanical function
Meets the product standard's requirements.

Additional information

Features
Connectable
EMC-version
RAL-number
7035
Suitable for
Metrical mounting

ETIM for 119200 Cabinets and enclosures (EC000261)
Feature Name Feature Value
Width (EF000008) 585 mm
Height (EF000040) 1210 mm
Depth (EF000049) 185 mm
Material (EF002169) Steel
Material quality (EF001257) Other
Surface finishing (EF006569) Powder coated
Colour (EF000007) Grey
RAL-number (EF000116) 7035
Freestanding (EF020363) No
Floor standing wall model (EF015208) No
Suitable for wall mounting (EF000664) No
Corner model (EF020814) No
Intermediate mounting (EF022994) No
Couplable (EF001229) Yes
With mounting plate (EF000118) No
Mounting plate depth-adjustable (EF006054) No
Suitable for wall built-in (EF007536) No
Pole fastening (EF009582) No
With door (EF009169) No
Number of doors (EF000122) 0
With glazed door (EF001089) No
With ventilation door (EF006279) No
With rear door (EF007381) No
Number of locks (EF000123) 0
With cover (EF007965) No
Transparent cover (EF011401) No
Suitable for metrical mounting (EF005823) Yes
Pitched roof (EF009278) No
Number of connector holes (EF005554) 0
Pre-stamping (EF001039) No
EMC-version (EF001062) Yes
Impact strength (EF004293) IK07
Degree of protection (IP) (EF005474) Other
Degree of protection (NEMA) (EF011959) Other
Thermal dissipation (Delta T = 20 K) according to IEC/TR 60890 (EF014986) 0 W
Max. permissible load of the enclosure according to IEC 62208 (EF014987) 0 N
Max. permissible load of the door(s) according to IEC 62208 (EF014988) 0 N
Max. permissible load of the mounting plate according to IEC 62208 (EF014989) 0 N

Product Datasheet