View larger
DS7-34DSX081N0-D 134955 Y7-134955 EATON ELECTRIC Soft starter, 81 A, 200 480 V AC, 24 V DC, Frame size: FS3,..
DS7-34DSX081N0-D
134955
Y7-134955
EATON - MOELLER
1 Pcs.
Automation > Soft starter
Standard Soft Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Supplied by Eaton Moeller, the DS7-34DSX081N0-D is a compact soft starter engineered to deliver efficient motor control within limited panel spaces. Industrial automation builders integrate these units to regulate starting voltage profiles and protect mechanical drive components from sudden torque spikes.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated operation current Ie at 40 °C Tu (EF007039): 81 A
- Rated operating voltage Ue (EF002418): 230 V
- Rated power three-phase motor, inline, at 230 V (EF007053): 22 kW
- Rated power three-phase motor, inline, at 400 V (EF007054): 45 kW
- Function (EF000030): Single direction
- Internal bypass (EF009214): Yes
- With display (EF000458): No
- Torque control (EF009215): No
- Rated surrounding temperature without derating (EF007074): 40 °C
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): DC
- Integrated motor overload protection (EF007297): No
- Degree of protection (IP) (EF005474): IP20
- Degree of protection (NEMA) (EF011959): 1
More info
▲General specifications
C-Tick Compliant
CSA Certified
IEC 60947-4-2
UL Listed
CSA22.2-14
UL
UL 508
CSA-C22.2 No 0-M91
CSA
C-Tick
UkrSEPRO
GB 14048.6
CSA-C22.2 No 14-05
CE
IEC/EN 60947-4-2
Features & Functions
Internal bypass contacts
Single direction
Min. ramp time 1 s - fast switching (semiconductor contactor)
Suppression of DC components for motors
Soft start function
Potential isolation between power and control sections
Suppression of closing transients
General
NEMA 1
4
FS3
Ambient conditions, mechanical
Climatic environmental conditions
Above 1000 m with 1 % derating per 100 m
Damp heat, constant, to IEC 60068-2-3
Main conducting paths
NZMN1-M100, Type “1” coordination, Main conducting paths
Motor rating
Terminal capacities
9 x 9 x 0.8 mm, Main cables
2 x (0.5 - 0.75) mm², Control circuit cables
2 x (6 - 25) mm², Main cables
1 x (0.5 - 2.5) mm², Control circuit cables
1 x (25 - 70) mm², Main cables
1 x (12 - 2/0), Main cables
1 x (21 - 14), Control circuit cables
1 x (25 - 70) mm², Main cables
2 x (0.5 - 1.0) mm², Control circuit cables
2 x (6 - 25) mm², Main cables
PZ2, 1 x 6 mm, Terminal screw, Standard screwdriver
0.4 Nm, Screw terminals, Control circuit cables
6 Nm (≤ 10 mm²)
Control circuit
50 mA, Control circuit, Regulator supply
1.6 mA, Control circuit, Digital inputs, External 24 V
Input/Output
24 V DC
Soft start function
Min. 30 %, Soft start function, Start voltage = turn-off voltage