View larger
DS7-34DSX024N0-D 134949 Y7-134949 EATON ELECTRIC Soft starter, 24 A, 200 480 V AC, 24 V DC, Frame size: FS2,..
DS7-34DSX024N0-D
134949
Y7-134949
EATON - MOELLER
1 Pcs.
Automation > Soft starter
Standard Soft Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller DS7-34DSX024N0-D is an Eaton Electric soft starter engineered to govern motor ramp-up phases by gradually increasing voltage to limit starting current and mechanical shock. Units of this type are widely implemented across industrial machinery, pumps, and conveyor systems to protect mechanical drive trains from aggressive torque spikes during startup.
Exact pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Rated operation current Ie at 40 °C Tu (EF007039): 24 A
- Rated operating voltage Ue (EF002418): 230 V
- Rated power three-phase motor, inline, at 230 V (EF007053): 5.5 kW
- Rated power three-phase motor, inline, at 400 V (EF007054): 11 kW
- Function (EF000030): Single direction
- Internal bypass (EF009214): Yes
- With display (EF000458): No
- Torque control (EF009215): No
- Rated surrounding temperature without derating (EF007074): 40 °C
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): DC
- Integrated motor overload protection (EF007297): No
- Degree of protection (IP) (EF005474): IP20
- Degree of protection (NEMA) (EF011959): 1
More info
▲General specifications
CSA-C22.2 No 0-M91
C-Tick
CSA22.2-14
CSA-C22.2 No 14-05
CSA
CE
UL 508
IEC/EN 60947-4-2
UL
UkrSEPRO
Features & Functions
Internal bypass
Suppression of closing transients
Potential isolation between power and control sections
Single direction
Soft start function
Current limitation, with PKE
Suppression of DC components for motors
General
IP20
Ambient conditions, mechanical
Climatic environmental conditions
Above 1000 m with 1 % derating per 100 m
Damp heat, cyclic, to IEC 60068-2-30
Main conducting paths
PKM0-25 (+ CL-PKZ0), Type “1” coordination, Main conducting paths
Motor rating
Terminal capacities
1 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 16) mm², Main cables
2 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 4) mm², Control circuit cables
2 x (0.75 - 10) mm², Main cables
1 x (0.75 - 16) mm², Main cables
18 - 6, Main cables
0.6 x 5.5 mm/1 x 6 mm, Terminal screws, Control circuit cables
1.2 Nm, Screw terminals, Control circuit cables
Control circuit
50 mA, Control circuit, Regulator supply
Input/Output
24 V DC
Soft start function
Min. 30 %, Soft start function, Start voltage = turn-off voltage