DS7-34DSX100N0-D 134956 Y7-134956 EATON ELECTRIC Soft starter, 100 A, 200 480 V AC, 24 V DC, Frame size: FS3..
DS7-34DSX100N0-D
134956
Y7-134956
EATON - MOELLER
1 Pcs.
Automation > Soft starter
Standard Soft Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for versatile motor management, this Eaton Moeller soft starter offers precise control over the acceleration phase of standard alternating current machinery. Industrial systems integrate these components to eliminate sudden mechanical jolts during startup, minimizing wear on system components and protecting electrical distribution networks.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated operation current Ie at 40 °C Tu (EF007039): 100 A
- Rated operating voltage Ue (EF002418): 230 V
- Rated power three-phase motor, inline, at 230 V (EF007053): 30 kW
- Rated power three-phase motor, inline, at 400 V (EF007054): 55 kW
- Function (EF000030): Single direction
- Internal bypass (EF009214): Yes
- With display (EF000458): No
- Torque control (EF009215): No
- Rated surrounding temperature without derating (EF007074): 40 °C
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): DC
- Integrated motor overload protection (EF007297): No
- Degree of protection (IP) (EF005474): IP20
- Degree of protection (NEMA) (EF011959): 1
More info
▲General specifications
CE Marked
EN 60947-4-2
CSA Certified
IEC 60947-4-2
CSA-C22.2 No 0-M91
C-Tick
CSA22.2-14
CSA-C22.2 No 14-05
CE
GB 14048.6
UkrSEPRO
IEC/EN 60947-4-2
UL 508
UL
CSA
Features & Functions
Internal bypass contacts
Current limitation, with PKE
Potential isolation between power and control sections
Soft start function
Suppression of closing transients
Suppression of DC components for motors
Single direction
General
NEMA 1
3
FS3
Ambient conditions, mechanical
Climatic environmental conditions
Above 1000 m with 1 % derating per 100 m
Damp heat, cyclic, to IEC 60068-2-30
Main conducting paths
NZMN1-M100, Type “1” coordination, Main conducting paths
Motor rating
Terminal capacities
2 x 9 x 0.8 mm, Main cables
2 x (0.5 - 0.75) mm², Control circuit cables
1 x (25 - 70) mm², Main cables
2 x (0.5 - 1.0) mm², Control circuit cables
2 x (6 - 25) mm², Main cables
1 x (12 - 2/0), Main cables
1 x (21 - 14), Control circuit cables
1 x (25 - 70) mm², Main cables
2 x (6 - 25) mm², Main cables
2 x (0.5 - 1.0) mm², Control circuit cables
PZ2, 1 x 6 mm, Terminal screw, Standard screwdriver
9 Nm (> 10 mm²)
0.4 Nm, Screw terminals, Control circuit cables
Control circuit
0,6 A/50 ms, Control circuit, Regulator supply at peak performance (close bypass) at 24 V DC
50 mA, Control circuit, Regulator supply
Input/Output
24 V DC (-15 %/+10 %) or via SmartWire-DT
Soft start function
Min. 30 %, Soft start function, Start voltage = turn-off voltage