View larger
S811+V72P3S 169006 Y7-169006 EATON ELECTRIC Soft starter, 720 A, 200 600 V AC, Us 24 V DC, with control unit..
S811+V72P3S
169006
Y7-169006
EATON - MOELLER
1 Pcs.
Automation > Soft starter
High Performance Soft Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller S811+V72P3S is a high-capacity soft starter engineered to regulate motor startup and deceleration profiles in industrial automation systems. Units of this type protect mechanical gear trains and reduce electrical grid stress by limiting inrush current during startup sequences.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated operation current Ie at 40 °C Tu (EF007039): 720 A
- Rated operating voltage Ue (EF002418): 200 V
- Rated power three-phase motor, inline, at 230 V (EF007053): 200 kW
- Rated power three-phase motor, inline, at 400 V (EF007054): 400 kW
- Function (EF000030): Single direction
- Internal bypass (EF009214): Yes
- With display (EF000458): Yes
- Torque control (EF009215): No
- Rated surrounding temperature without derating (EF007074): 50 °C
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): DC
- Integrated motor overload protection (EF007297): Yes
- Release class (EF006668): Adjustable
- Degree of protection (IP) (EF005474): IP20
More info
▲General specifications
CSA-C22.2 No. 14
UL 508
UL File No.: E202571
C-Tick
CSA Class No.: 3211-06
UL Category Control No.: NMFT
IEC/EN 60947-4-2
GB14048
CCC
CE
CSA22.2-14-1995
UL
CSA
Features & Functions
Display
Internal bypass contacts
Motor overload protection
Min. ramp time 1 s - fast switching (semiconductor contactor)
Suppression of DC components for motors
Soft start function
Current limitation
Suppression of closing transients
Potential isolation between power and control sections
Underload monitoring
Overload monitoring
General
NEMA Other
CLASS 20 (heavy starting duty 3 x Iₑ for 45 s)
CLASS 30 (6 x Iₑ for 30 s)
Climatic environmental conditions
Max. 2000 m
Damp heat, constant, to IEC 60068-2-3
Main conducting paths
Motor rating
Terminal capacities
2 x (1 - 2.5) mm², Control circuit cables
6 x (120 - 240) mm², Main cables
1 x (2.5 - 4) mm², Control circuit cables
2 x (120 - 240) mm², Main cables
1 x (2.5 - 4) mm², Control circuit cables
2 x (1 - 2.5) mm², Control circuit cables
6 x (120 - 240) mm², Main cables
2 x (120 - 240) mm², Main cables
1 x (14 - 12), Control circuit cables
6 x (4 - 500 kcmil), Main cables
2 x (4 - 500 kcmil), Main cables
2 x (14 - 12), Control circuit cables
2 x (1 - 2.5) mm², Control circuit cables
2 x (120 - 240) mm², Main cables
4 x (70 - 240) mm², Main cables
1 x (2.5 - 4) mm², Control circuit cables
Control circuit
1400 mA, Control circuit, Regulator supply
100 mA, Control circuit, Digital inputs, External 24 V (no-load)
150 mA, Control circuit, Digital inputs, External 24 V
Input/Output
24 V DC (-10 %/+10 %)
Soft start function
Max. 2000 ms (Kickstart Duration)