View larger
S811+V72N3S 169005 S811PLUSV72N3S EATON ELECTRIC Soft starter, 720 A, 200 600 V AC, Us 24 V DC, with control..
S811+V72N3S
169005
S811PLUSV72N3S
EATON - MOELLER
1 Pcs.
Automation > Soft starter
High Performance Soft Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller part S811+V72N3S serves as a high-capacity soft starter designed to control heavy industrial motors by smoothing out startup voltage and managing torque output. Such controllers prevent premature wear on mechanical couplings and reduce peak electrical demands across facility distribution networks.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated operation current Ie at 40 °C Tu (EF007039): 720 A
- Rated operating voltage Ue (EF002418): 200 V
- Rated power three-phase motor, inline, at 230 V (EF007053): 200 kW
- Rated power three-phase motor, inline, at 400 V (EF007054): 400 kW
- Function (EF000030): Single direction
- Internal bypass (EF009214): Yes
- With display (EF000458): Yes
- Torque control (EF009215): No
- Rated surrounding temperature without derating (EF007074): 50 °C
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): DC
- Integrated motor overload protection (EF007297): Yes
- Release class (EF006668): Adjustable
- Degree of protection (IP) (EF005474): IP20
More info
▲General specifications
CSA File No.: LR 353
CSA
GB14048
CCC
CE
CSA Class No.: 3211-06
UL
UL 508
C-Tick
CSA-C22.2 No. 14
IEC/EN 60947-4-2
UL Category Control No.: NMFT
UL File No.: E202571
Features & Functions
Internal bypass contacts
Internal bypass
Motor overload protection
Current limitation
Underload monitoring
Soft start function
Overload monitoring
Single direction
Min. ramp time 1 s - fast switching (semiconductor contactor)
Suppression of closing transients
Potential isolation between power and control sections
General
NEMA Other
CLASS 10 (star-delta replacement)
CLASS 30 (6 x Iₑ for 30 s)
Climatic environmental conditions
Max. 2000 m
Damp heat, cyclic, to IEC 60068-2-30
Main conducting paths
Motor rating
Terminal capacities
2 x (1 - 2.5) mm², Control circuit cables
2 x (120 - 240) mm², Main cables
1 x (2.5 - 4) mm², Control circuit cables
4 x (70 - 240) mm², Main cables
2 x (120 - 240) mm², Main cables
4 x (70 - 240) mm², Main cables
1 x (2.5 - 4) mm², Control circuit cables
6 x (120 - 240) mm², Main cables
6 x (4 - 500 kcmil), Main cables
2 x (14 - 12), Control circuit cables
2 x (4 - 500 kcmil), Main cables
1 x (14 - 12), Control circuit cables
1 x (2.5 - 4) mm², Control circuit cables
2 x (1 - 2.5) mm², Control circuit cables
4 x (70 - 240) mm², Main cables
6 x (120 - 240) mm², Main cables
Control circuit
100 mA, Control circuit, Digital inputs, External 24 V (no-load)
1400 mA, Control circuit, Regulator supply
10 A/150 ms, Control circuit, Regulator supply at peak performance (close bypass) at 24 V DC
Input/Output
24 V DC
Soft start function
Max. 2000 ms (Kickstart Duration)