View larger
S811+N66N3S 168978 S811PLUSN66N3S EATON ELECTRIC Soft starter, 66 A, 200 600 V AC, Us 24 V DC, with control ..
S811+N66N3S
168978
S811PLUSN66N3S
EATON - MOELLER
1 Pcs.
Automation > Soft starter
High Performance Soft Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Providing precise electronic motor management, an Eaton Moeller electric soft starter regulates voltage application to ensure controlled acceleration of industrial machinery. Such devices are implemented across manufacturing environments to protect drive belts, shafts, and connected loads from destructive starting torque peaks. Integrated motor overload protection safeguards equipment against thermal damage.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated operation current Ie at 40 °C Tu (EF007039): 66 A
- Rated operating voltage Ue (EF002418): 200 V
- Rated power three-phase motor, inline, at 230 V (EF007053): 18.5 kW
- Rated power three-phase motor, inline, at 400 V (EF007054): 30 kW
- Function (EF000030): Single direction
- Internal bypass (EF009214): Yes
- With display (EF000458): Yes
- Torque control (EF009215): No
- Rated surrounding temperature without derating (EF007074): 50 °C
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): DC
- Integrated motor overload protection (EF007297): Yes
- Release class (EF006668): Adjustable
- Degree of protection (IP) (EF005474): IP00
More info
▲General specifications
IEC 60947-4-2
UL Recognized
EN 60947-4-2
UL Listed
CSA Certified for Elevator Duty
GB14048
UL File No.: E202571
CSA File No.: LR 353
UL Category Control No.: NMFT
CE
CCC
CSA
C-Tick
CSA Class No.: 3211-06, 2411-01
UL 508
CSA-C22.2 No. 14
IEC/EN 60947-4-2
CSA22.2-14-1995
UL
Features & Functions
Motor overload protection
Display
Internal bypass
Overload monitoring
Potential isolation between power and control sections
Suppression of DC components for motors
Current limitation
Single direction
Soft start function
Suppression of closing transients
Underload monitoring
General
NEMA Other
CLASS 30 (6 x Iₑ for 30 s)
CLASS 20 (heavy starting duty 3 x Iₑ for 45 s)
Climatic environmental conditions
Max. 2000 m
Damp heat, constant, to IEC 60068-2-3
Main conducting paths
Motor rating
Terminal capacities
1 x (2.5 - 35) mm², Main cables
2 x (1 - 2.5) mm², Control circuit cables
1 x (2.5 - 35) mm², Main cables
2 x (1 - 2.5) mm², Control circuit cables
1 x (14 - 2), Main cables
1 x (14 - 12), Control circuit cables
1 x (2.5 - 4) mm², Control circuit cables
1 x (2.5 - 35) mm², Main cables
1.5 x 6 mm, Terminal screw, Main cables
0.4 Nm, Screw terminals, Control circuit cables
4 Nm (≤ 6 mm²)
5 Nm (≤ 25 mm²)
4.5 Nm (≤ 10 mm²)
Control circuit
100 mA, Control circuit, Digital inputs, External 24 V (no-load)
150 mA, Control circuit, Digital inputs, External 24 V
10 A/150 ms, Control circuit, Regulator supply at peak performance (close bypass) at 24 V DC
Input/Output
24 V DC (-10 %/+10 %)
Soft start function
100% (Kickstart voltage)