View larger
DS7-342SX055N0-N 134935 Y7-134935 EATON ELECTRIC Soft starter, 55 A, 200 480 V AC, Us 110 230 V AC, Frame si..
DS7-342SX055N0-N
134935
Y7-134935
EATON - MOELLER
1 Pcs.
Automation > Soft starter
Standard Soft Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller DS7-342SX055N0-N soft starter controls three-phase AC motors by gradually increasing voltage to eliminate sudden mechanical jolts. These components are standard in automated production lines to safeguard pumps, compressors, and material handling systems from wear. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated operation current Ie at 40 °C Tu (EF007039): 55 A
- Rated operating voltage Ue (EF002418): 230 V
- Rated power three-phase motor, inline, at 230 V (EF007053): 15 kW
- Rated power three-phase motor, inline, at 400 V (EF007054): 30 kW
- Function (EF000030): Single direction
- Internal bypass (EF009214): Yes
- With display (EF000458): No
- Torque control (EF009215): No
- Rated surrounding temperature without derating (EF007074): 40 °C
- Rated control supply voltage AC 50 Hz (EF003978): 110 V
- Rated control supply voltage AC 60 Hz (EF003979): 110 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Integrated motor overload protection (EF007297): No
- Degree of protection (IP) (EF005474): IP20
- Degree of protection (NEMA) (EF011959): 1
More info
▲General specifications
CSA22.2-14
C-Tick
CSA Class No.: 321106
CSA-C22.2 No 0-M91
CSA
CE
GB 14048.6
UL 508
CSA-C22.2 No 14-05
UL
IEC/EN 60947-4-2
CSA File No.: 2511305
UL File No.: E251034
Features & Functions
Internal bypass contacts
Suppression of closing transients
Suppression of DC components for motors
Min. ramp time 1 s - fast switching (semiconductor contactor)
Soft start function
Potential isolation between power and control sections
General
NEMA 1
Ambient conditions, mechanical
Climatic environmental conditions
Above 1000 m with 1 % derating per 100 m
Damp heat, constant, to IEC 60068-2-3
Main conducting paths
NZMN1-M63/PKZM4-57, Type “1” coordination, Main conducting paths
Motor rating
Terminal capacities
2 x 9 x 0.8 mm, Main cables
1 x (0.5 - 1.5) mm², Control circuit cables
1 x (0.5 - 2.5) mm², Control circuit cables
2 x (6 - 25) mm², Main cables
2 x (0.5 - 1.0) mm², Control circuit cables
1 x (12 - 2/0), Main cables
2 x (21 - 18), Control circuit cables
1 x (0.5 - 1.5) mm², Control circuit cables
2 x (6 - 25) mm², Main cables
2 x (0.5 - 1.0) mm², Control circuit cables
PZ2, 1 x 6 mm, Terminal screw, Standard screwdriver
0.4 Nm, Screw terminals, Control circuit cables
9 Nm (> 10 mm²)
Control circuit
1.6 mA, Control circuit, Digital inputs, External 24 V
0,6 A/50 ms, Control circuit, Regulator supply at peak performance (close bypass) at 24 V DC
Input/Output
110 - 230 V AC (-15 %/+10 %)
Soft start function
Max. 100 %, Soft start function, Start voltage = turn-off voltage