View larger
DS7-340SX004N0-N 134847 Y7-134847 EATON ELECTRIC Soft starter, 4 A, 200 480 V AC, Us 24 V AC/DC, Frame size ..
DS7-340SX004N0-N
134847
Y7-134847
EATON - MOELLER
1 Pcs.
Automation > Soft starter
Standard Soft Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller soft starter, part number DS7-340SX004N0-N, regulates the voltage supplied to three-phase electric motors during startup to limit mechanical shock and inrush current. Such solid-state controllers are commonly deployed in industrial automation setups to protect belts, pumps, and gearboxes from high starting torque.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated operation current Ie at 40 °C Tu (EF007039): 4 A
- Rated operating voltage Ue (EF002418): 230 V
- Rated power three-phase motor, inline, at 230 V (EF007053): 0.75 kW
- Rated power three-phase motor, inline, at 400 V (EF007054): 1.5 kW
- Function (EF000030): Single direction
- Internal bypass (EF009214): Yes
- With display (EF000458): No
- Torque control (EF009215): No
- Rated surrounding temperature without derating (EF007074): 40 °C
- Rated control supply voltage AC 50 Hz (EF003978): 24 V
- Rated control supply voltage AC 60 Hz (EF003979): 24 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): AC/DC
- Integrated motor overload protection (EF007297): No
- Degree of protection (IP) (EF005474): IP20
- Degree of protection (NEMA) (EF011959): 1
More info
▲General specifications
CSA Std. C22.2 No. 14-05
CSA Std. C22.2 No. 0-M91
IEC 60947-4-2
EN 60947-4-2
CSA File No.: 2511305
UL File No.: E251034
CSA-C22.2 No 0-M91
CSA Class No.: 321106
GB 14048.6
CSA-C22.2 No 14-05
IEC/EN 60947-4-2
CSA
C-Tick
CSA22.2-14
UL
CE
UkrSEPRO
Features & Functions
Internal bypass
Min. ramp time 1 s - fast switching (semiconductor contactor)
Suppression of closing transients
Single direction
Soft start function
Suppression of DC components for motors
General
NEMA 1
Ambient conditions, mechanical
Climatic environmental conditions
Max. 2000 m
Damp heat, cyclic, to IEC 60068-2-30
Main conducting paths
PKM0-4 (+ CL-PKZ0), Type “1” coordination, Main conducting paths
Motor rating
Terminal capacities
1 x (0.75 - 2.5) mm², Main cables
2 x (0.75 - 2.5) mm², Main cables
1 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Main cables
1 x (0.75 - 4) mm², Control circuit cables
1 x (0.75 - 4) mm², Main cables
18 - 10, Control circuit cables
0.6 x 5.5 mm/1 x 6 mm, Terminal screws, Control circuit cables
1.2 Nm
Control circuit
50 mA, Control circuit, Regulator supply
0 - 3 V, DC operated
Input/Output
24 V AC
24 V DC
24 V DC (-15 %/+10 %)
Soft start function
Max. 100 %, Soft start function, Start voltage = turn-off voltage