Request QuoteProduct Overview
High-capacity motor management is handled by the S811+V36V3S Eaton Moeller soft starter, built to regulate starting voltage and current profiles for large industrial assets. These robust controllers prevent mechanical stress on shafts and couplings while minimizing voltage dips across plant electrical buses.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated operation current Ie at 40 °C Tu (EF007039): 360 A
- Rated operating voltage Ue (EF002418): 200 V
- Rated power three-phase motor, inline, at 230 V (EF007053): 110 kW
- Rated power three-phase motor, inline, at 400 V (EF007054): 200 kW
- Function (EF000030): Single direction
- Internal bypass (EF009214): Yes
- With display (EF000458): Yes
- Torque control (EF009215): No
- Rated surrounding temperature without derating (EF007074): 50 °C
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): DC
- Integrated motor overload protection (EF007297): Yes
- Release class (EF006668): Adjustable
- Degree of protection (IP) (EF005474): IP00
More info
▲General specifications
UL Category Control No.: NMFT
GB14048
CE
UL File No.: E202571
UL 508
CSA22.2-14-1995
UL
CCC
CSA
IEC/EN 60947-4-2
Features & Functions
Internal bypass contacts
Internal bypass
Motor overload protection
Underload monitoring
Min. ramp time 1 s - fast switching (semiconductor contactor)
Soft start function
Current limitation
Potential isolation between power and control sections
Overload monitoring
Suppression of DC components for motors
Single direction
General
NEMA Other
CLASS 30 (6 x Iₑ for 30 s)
CLASS 10 (star-delta replacement)
Climatic environmental conditions
Above 2000 m with 0.5 % derating per 100 m
Damp heat, cyclic, to IEC 60068-2-30
Main conducting paths
Motor rating
Terminal capacities
2 x (120 - 240) mm², Main cables
6 x (120 - 240) mm², Main cables
4 x (70 - 240) mm², Main cables
1 x (2.5 - 4) mm², Control circuit cables
1 x (2.5 - 4) mm², Control circuit cables
2 x (120 - 240) mm², Main cables
2 x (1 - 2.5) mm², Control circuit cables
6 x (120 - 240) mm², Main cables
1 x (14 - 12), Control circuit cables
2 x (4 - 500 kcmil), Main cables
6 x (4 - 500 kcmil), Main cables
2 x (14 - 12), Control circuit cables
2 x (1 - 2.5) mm², Control circuit cables
6 x (120 - 240) mm², Main cables
1 x (2.5 - 4) mm², Control circuit cables
4 x (70 - 240) mm², Main cables
Control circuit
1400 mA, Control circuit, Regulator supply
10 A/150 ms, Control circuit, Regulator supply at peak performance (close bypass) at 24 V DC
150 mA, Control circuit, Digital inputs, External 24 V
Input/Output
24 V DC (-10 %/+10 %)
Soft start function
100% (Kickstart voltage)