View larger
DS7-340SX032N0-N 134914 Y7-134914 EATON ELECTRIC Soft starter, 3p, 32A, 200-480VAC, us 24VAC/DC
DS7-340SX032N0-N
134914
Y7-134914
EATON - MOELLER
1 Pcs.
Automation > Soft starter
Standard Soft Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller part DS7-340SX032N0-N functions as a compact electronic soft starter engineered to regulate starting parameters for three-phase industrial motors. Panel builders deploy these units to eliminate mechanical shocks and protect downstream components from high inrush currents during system startup.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated operation current Ie at 40 °C Tu (EF007039): 32 A
- Rated operating voltage Ue (EF002418): 230 V
- Rated power three-phase motor, inline, at 230 V (EF007053): 7.5 kW
- Rated power three-phase motor, inline, at 400 V (EF007054): 15 kW
- Function (EF000030): Single direction
- Internal bypass (EF009214): Yes
- With display (EF000458): No
- Torque control (EF009215): No
- Rated surrounding temperature without derating (EF007074): 40 °C
- Rated control supply voltage AC 50 Hz (EF003978): 24 V
- Rated control supply voltage AC 60 Hz (EF003979): 24 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): AC/DC
- Integrated motor overload protection (EF007297): No
- Degree of protection (IP) (EF005474): IP20
- Degree of protection (NEMA) (EF011959): 1
More info
▲General specifications
CSA Std. C22.2 No. 0-M91
CSA Std. C22.2 No. 14-05
IEC 60947-4-2
EN 60947-4-2
C-Tick
CSA22.2-14
UL File No.: E251034
CSA File No.: 2511305
CSA-C22.2 No 14-05
UL
UkrSEPRO
GB 14048.6
CE
CSA-C22.2 No 0-M91
CSA
IEC/EN 60947-4-2
CSA Class No.: 321106
Features & Functions
Internal bypass contacts
Suppression of DC components for motors
Soft start function
Single direction
Suppression of closing transients
Min. ramp time 1 s - fast switching (semiconductor contactor)
General
IP20
Ambient conditions, mechanical
Climatic environmental conditions
Max. 2000 m
Damp heat, constant, to IEC 60068-2-3
Main conducting paths
PKM0-32 (+ CL-PKZ0), Type “1” coordination, Main conducting paths
Motor rating
Terminal capacities
2 x (0.75 - 10) mm², Main cables
1 x (0.5 - 1.5) mm², Control circuit cables
1 x (0.75 - 16) mm², Main cables
1 x (0.5 - 2.5) mm², Control circuit cables
2 x (0.5 - 1.0) mm², Control circuit cables
1 x (0.75 - 16) mm², Main cables
2 x (21 - 18), Control circuit cables
18 - 6, Main cables
1 x 16 mm², Main cables
2 x (0.5 - 1.0) mm², Control circuit cables
0.6 x 3.5 mm, Terminal screws, Control circuit cables
1.2 Nm, Screw terminals, Control circuit cables
Control circuit
1.6 mA, Control circuit, Digital inputs, External 24 V
0 - 3 V, DC operated
Input/Output
24 V DC
24 V DC (-15 %/+10 %)
24 V AC (-15 %/+10 %)
Soft start function
Max. 100 %, Soft start function, Start voltage = turn-off voltage