View larger
DS7-342SX160N0-N 134940 Y7-134940 EATON ELECTRIC Soft starter, 3p, 160A, 200-480VAC, us 110/230VAC
DS7-342SX160N0-N
134940
Y7-134940
EATON - MOELLER
1 Pcs.
Automation > Soft starter
Standard Soft Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller soft starter serves as a solid-state switching solution designed to manage starting characteristics and reduce mechanical wear on industrial motor installations. It ensures controlled ramp-up times for standard AC machinery, minimizing disruptive voltage drops across plant distribution networks.
Specific pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated operation current Ie at 40 °C Tu (EF007039): 160 A
- Rated operating voltage Ue (EF002418): 230 V
- Rated power three-phase motor, inline, at 230 V (EF007053): 45 kW
- Rated power three-phase motor, inline, at 400 V (EF007054): 90 kW
- Function (EF000030): Single direction
- Internal bypass (EF009214): Yes
- With display (EF000458): No
- Torque control (EF009215): No
- Rated surrounding temperature without derating (EF007074): 40 °C
- Rated control supply voltage AC 50 Hz (EF003978): 110 V
- Rated control supply voltage AC 60 Hz (EF003979): 110 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Integrated motor overload protection (EF007297): No
- Degree of protection (IP) (EF005474): IP20
- Degree of protection (NEMA) (EF011959): 1
More info
▲General specifications
UL
UL File No.: E251034
C-Tick
CSA-C22.2 No 0-M91
CSA22.2-14
CSA File No.: 2511305
GB 14048.6
UL 508
UkrSEPRO
IEC/EN 60947-4-2
CSA-C22.2 No 14-05
CE
CSA
Features & Functions
Internal bypass
Min. ramp time 1 s - fast switching (semiconductor contactor)
Single direction
Suppression of closing transients
Soft start function
Suppression of DC components for motors
General
NEMA 1
Ambient conditions, mechanical
Climatic environmental conditions
Max. 2000 m
Damp heat, cyclic, to IEC 60068-2-30
Main conducting paths
3 x 170M5008, Type „2“ coordination (additional with the fuses for coordination type „1“), Main conducting paths
Motor rating
Terminal capacities
10 x 16 x 0.8 mm, Main cables
2 x (0.5 - 0.75) mm², Control circuit cables
2 x (4 - 70) mm², Main cables
1 x (4 - 185) mm², Main cables
1 x (0.5 - 2.5) mm², Control circuit cables
2 x (21 - 18), Control circuit cables
1 x (21 - 14), Control circuit cables
2 x (12 - 00), Main cables
2 x (0.5 - 1.0) mm², Control circuit cables
2 x (4 - 70) mm², Main cables
1 x (4 - 185) mm², Main cables
0.6 x 3.5 mm, Terminal screws, Control circuit cables
5 Nm (≤ 10 mm²)
0.4 Nm, Screw terminals, Control circuit cables
Control circuit
50 mA, Control circuit, Regulator supply
1.6 mA, Control circuit, Digital inputs, External 24 V
Input/Output
110 - 230 V AC
Soft start function
Max. 100 %, Soft start function, Start voltage = turn-off voltage