View larger
DS7-340SX012N0-N 134911 Y7-134911 EATON ELECTRIC Soft starter, 3p, 12A, 200-480VAC, us 24VAC/DC
DS7-340SX012N0-N
134911
Y7-134911
EATON - MOELLER
1 Pcs.
Automation > Soft starter
Standard Soft Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller soft starter provides reliable three-phase motor management for standard industrial machinery. By controlling voltage ramps during startup, it prevents abrupt mechanical shock and extends the operational lifecycle of connected drives.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Rated operation current Ie at 40 °C Tu (EF007039): 12 A
- Rated operating voltage Ue (EF002418): 230 V
- Rated power three-phase motor, inline, at 230 V (EF007053): 3 kW
- Rated power three-phase motor, inline, at 400 V (EF007054): 5.5 kW
- Function (EF000030): Single direction
- Internal bypass (EF009214): Yes
- With display (EF000458): No
- Torque control (EF009215): No
- Rated surrounding temperature without derating (EF007074): 40 °C
- Rated control supply voltage AC 50 Hz (EF003978): 24 V
- Rated control supply voltage AC 60 Hz (EF003979): 24 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): AC/DC
- Integrated motor overload protection (EF007297): No
- Degree of protection (IP) (EF005474): IP20
- Degree of protection (NEMA) (EF011959): 1
More info
▲General specifications
CSA Class No.: 321106
UL
UkrSEPRO
CE
CSA-C22.2 No 0-M91
IEC/EN 60947-4-2
GB 14048.6
CSA
UL 508
CSA22.2-14
CSA-C22.2 No 14-05
C-Tick
UL File No.: E251034
Features & Functions
Internal bypass
Suppression of DC components for motors
Min. ramp time 1 s - fast switching (semiconductor contactor)
Soft start function
Potential isolation between power and control sections
Suppression of closing transients
General
NEMA 1
Ambient conditions, mechanical
Climatic environmental conditions
Above 1000 m with 1 % derating per 100 m
Damp heat, cyclic, to IEC 60068-2-30
Main conducting paths
3 x 170M1362, Type „2“ coordination (additional with the fuses for coordination type „1“), Main conducting paths
Motor rating
Terminal capacities
1 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
1 x (0.75 - 2.5) mm², Main cables
1 x (0.75 - 4) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Control circuit cables
2 x (0.75 - 2.5) mm², Main cables
18 - 10, Control circuit cables
0.6 x 5.5 mm/1 x 6 mm, Terminal screws, Control circuit cables
1.2 Nm, Screw terminals, Control circuit cables
Control circuit
1.6 mA, Control circuit, Digital inputs, External 24 V
AC operated: 0 - 3 V, AC operated
Input/Output
24 V AC
24 V AC (-15 %/+10 %)
24 V DC (-15 %/+10 %)
Soft start function
Min. 30 %, Soft start function, Start voltage = turn-off voltage