NZM1-XAHIV60AC/DC 259778 Y7-259778 EATON ELECTRIC Shunt release, 60VAC/DC, +1early N/O
NZM1-XAHIV60AC/DC
259778
Y7-259778
EATON - MOELLER
1 Pcs.
Automation > Shunt release (for power circuit breaker)
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller shunt release with early auxiliary contact (NZM1-XAHIV60AC/DC) enables remote tripping of off-load switches while providing early status feedback through its integrated normally open contact. This combination supports advanced control logic and interlocking sequences in electrical switchgear.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 60 V
- Rated control supply voltage AC 60 Hz (EF003979): 60 V
- Rated control supply voltage DC (EF003980): 60 V
- Voltage type for actuating (EF008242): AC
- Type of electric connection (EF003961): Screw connection
- Number of contacts as normally open contact (EF008256): 1
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as change-over contact (EF008257): 0
- Suitable for power circuit breaker (EF005863): No
- Suitable for off-load switch (EF001543): Yes
- Suitable for motor safety switch (EF005826): No
- Suitable for overload relay (EF001545): No
More info
▲General specifications
IEC
RoHS conform
UL (File No. E140305)
UL (Category Control Number DIHS)
CSA-C22.2 No. 5-09
CSA (Class No. 1437-01)
CSA (File No. 22086)
UL489
CSA certified
IEC60947
UL listed
Product specifications
- Cannot be used in conjunction with NZM...-XR... remote operator.
- If the shunt trip is live, contact with the circuit breaker’s primary contacts is prevented when switched on.
- Early make of auxiliary contact on switching on and off (manual operation): approx. 20 ms.
- Shunt releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XU... undervoltage release.
With 3 m connection cable instead of screw termination
0.75 mm² - 2.5 mm² (2x) for undervoltage releases, off-delayed with ferrule
0.75 mm² - 2.5 mm² (1x) at shunt release with ferrule
0.75 mm² - 2.5 mm² (1x) for undervoltage releases, off-delayed with ferrule
18 - 14 AWG (1x) at shunt release
18 - 14 AWG (2x) at shunt release
18 - 14 AWG (1x) for undervoltage releases, off-delayed
18 - 14 AWG (2x) for undervoltage releases, off-delayed
60 V AC