NZM2/3-XAHIV380-440AC/DC 259820 Y7-259820 EATON ELECTRIC Shunt release, 380-440VAC/DC, +1early N/O
NZM2/3-XAHIV380-440AC/DC
259820
Y7-259820
EATON - MOELLER
1 Pcs.
Automation > Shunt release (for power circuit breaker)
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An NZM2/3-XAHIV380-440AC/DC 259820 Y7-259820 EATON ELECTRIC Shunt release functions as an internal electrical accessory that allows operators to remotely open protective switching devices in industrial power systems. These units are commonly deployed in automated safety shutdown circuits to isolate electrical loads when control signals are applied. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 380 V
- Rated control supply voltage AC 60 Hz (EF003979): 380 V
- Rated control supply voltage DC (EF003980): 380 V
- Voltage type for actuating (EF008242): AC/DC
- Type of electric connection (EF003961): Screw connection
- Number of contacts as normally open contact (EF008256): 1
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as change-over contact (EF008257): 0
- Suitable for power circuit breaker (EF005863): No
- Suitable for off-load switch (EF001543): Yes
- Suitable for motor safety switch (EF005826): No
- Suitable for overload relay (EF001545): No
More info
▲General specifications
IEC
RoHS conform
CSA (Class No. 1437-01)
UL (File No. E140305)
CSA (File No. 22086)
IEC60947
CSA certified
CE marking
CSA-C22.2 No. 5-09
UL489
UL (Category Control Number DIHS)
Product specifications
NZM3(-4), N(S)3(-4)
- Cannot be used in conjunction with NZM...-XR... remote operator.
- If the shunt trip is live, contact with the circuit breaker’s primary contacts is prevented when switched on.
- Early make of auxiliary contact on switching on and off (manual operation): approx. 20 ms.
- Shunt releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XU... undervoltage release.
0.75 mm² - 2.5 mm² (1x) for undervoltage releases, off-delayed with ferrule
0.75 mm² - 2.5 mm² (1x) at shunt release with ferrule
0.75 mm² - 2.5 mm² (2x) for undervoltage releases, off-delayed with ferrule
18 - 14 AWG (1x) for undervoltage releases, off-delayed
0.75 mm² - 2.5 mm² (2x) at shunt release with ferrule
18 - 14 AWG (2x) at shunt release
18 - 14 AWG (2x) for undervoltage releases, off-delayed
380 V AC
440 V AC
440 V DC