EATON - MOELLER +IZM-STS230AD +IZM-STS230AD 122743 EATON ELECTRIC Shunt release, (2), 208-250VAC/DC View larger
Images are for illustrative purposes only. Please refer to data sheet for details

+IZM-STS230AD 122743 EATON ELECTRIC Shunt release, (2), 208-250VAC/DC

+IZM-STS230AD

122743

EATON - MOELLER

1 Pcs.

Shunt release, (2), 208-250VAC/DC Shunt release, Voltage release, For use with: IZM20, 32, 40, 63…, IN20, 32,40, 63…, If ordered separately a secondary terminal unit IZM‐SEC‐… is necessary for connection. Order separately if required. Terminal assignment page 71

Automation > Shunt release (for power circuit breaker)
Circuit Breakers IZM

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Operating as a shunt release, this +IZM-STS230AD 122743 EATON ELECTRIC component enables remote tripping functionality for electrical switching devices within industrial power architectures. Circuit protection systems rely on these internal auxiliary releases to safely interrupt power feeds upon receiving an external control signal.

Pricing, availability, and lead time are confirmed per enquiry through an RFQ.

  • Rated control supply voltage AC 50 Hz (EF003978): None V
  • Rated control supply voltage AC 60 Hz (EF003979): None V
  • Rated control supply voltage DC (EF003980): None V
  • Power consumption (EF000346): None W
  • Suitable for power circuit breaker (EF005863): false
  • Suitable for off-load switch (EF001543): false
  • Suitable for motor safety switch (EF005826): false
  • Suitable for overload relay (EF001545): false

More info

Shunt release, (2), 208-250VAC/DC
Shunt release, Voltage release, For use with: IZM20, 32, 40, 63…, IN20, 32,40, 63…, If ordered separately a secondary terminal unit IZM‐SEC‐… is necessary for connection. Order separately if required. Terminal assignment page 71
[

Delivery program

Accessories
Voltage release
Accessories
2nd shunt release for 100 % duty factor
For use with
IZM20, 32, 40, 63…
IN20, 32,40, 63…
Instructions
If ordered separately a secondary terminal unit IZM‐SEC‐… is necessary for connection. Order separately if required. Terminal assignment page 71
,

Technical data

Rated control voltage [Us]
AC 50/60 Hz [Us]
208 - 240 V
DC [Us]
208 - 250 V
Power consumption
AC
(pick-up 450) VA
DC
(pick-up 450) W
Circuit-breaker response time at Us
35 ms
Operating range
Pick-up voltage [Pick-up]
0,85 - 1,1 x Uc
,

Design verification as per IEC/EN 61439

Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+70 °C
]