View larger
PKM0-6,3 072728 Y7-72728 EATON ELECTRIC Short-circuit protective breaker, 3p, im 88A
PKM0-6,3
072728
Y7-72728
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller PKM0-6,3 short-circuit protective breaker, 3p, im 88A is implemented in electrical distribution architectures to guard machinery against catastrophic short circuits. This specialized breaker disconnects faulty circuits instantly to protect sensitive automation hardware. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 0 A
- Adjustment range undelayed short-circuit release (EF007131): 98 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): No
- Switch off technique (EF007007): Magnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 6.3 A
- Rated operation power at AC-3, 230 V (EF007025): 1.1 kW
- Rated operation power at AC-3, 400 V (EF001364): 2.2 kW
- Power loss (EF005387): 5.68 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
IEC/EN 60947
Features & Functions
General
-25 - 55 °C, Operating range
≤ 0.25 %/K, residual error for T > 40°
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (1 - 6) mm², ferrule to DIN 46228
1 x (1 - 6) mm²
1 Nm, Screw terminals, Control circuit cables
Electrical rating
Short-circuit rating
Basic device fixed 15.5 x Iu, Trip Blocks
± 20% tolerance, Trip blocks