View larger
PKM0-2,5 072726 Y7-72726 EATON ELECTRIC Short-circuit protective breaker, 3p, im 35A
PKM0-2,5
072726
Y7-72726
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers PKZ
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for precise short-circuit isolation, the PKM0-2,5 072726 Y7-72726 EATON ELECTRIC Short-circuit protective breaker, 3p, im 35A operates as a dedicated motor feeder protector. Such protective breakers are typically installed inside electrical enclosures to safeguard downstream circuits against high fault currents. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 0 A
- Adjustment range undelayed short-circuit release (EF007131): 39 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): No
- Switch off technique (EF007007): Magnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 2.5 A
- Rated operation power at AC-3, 230 V (EF007025): 0.37 kW
- Rated operation power at AC-3, 400 V (EF001364): 0.75 kW
- Power loss (EF005387): 5.16 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
VDE 0660
Features & Functions
General
≤ 0.25 %/K, residual error for T > 40°
-25 - 55 °C, Operating range
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
2 x (1 - 6) mm², ferrule to DIN 46228
1 x (1 - 6) mm²
1 Nm, Screw terminals, Control circuit cables
Electrical rating
Short-circuit rating
38.8 A, Irm, Setting range max.
± 20% tolerance, Trip blocks