Request QuoteProduct Overview
An Eaton Moeller PKM0-10 short-circuit protective breaker provides magnetic fault protection for electrical installations and industrial machinery where precise short-circuit isolation is required.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 0 A
- Adjustment range undelayed short-circuit release (EF007131): 155 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): No
- Switch off technique (EF007007): Magnetic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 10 A
- Rated operation power at AC-3, 230 V (EF007025): 2.2 kW
- Rated operation power at AC-3, 400 V (EF001364): 4 kW
- Power loss (EF005387): 6.48 W
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rotating button
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
More info
▲General specifications
IEC/EN 60947
Features & Functions
General
-5 - 40 °C to IEC/EN 60947, VDE 0660
-25 - 55 °C, Operating range
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (1 - 6) mm², ferrule to DIN 46228
2 x (1 - 6) mm²
1 Nm, Screw terminals, Control circuit cables
Electrical rating
Short-circuit rating
± 20% tolerance, Trip blocks
Basic device fixed 15.5 x Iu, Trip Blocks