View larger
ESR5-NO-21-24VAC-DC 118700 Y7-118700 EATON ELECTRIC Safety relay emergency stop/protective door, 24VDC/AC, 2..
ESR5-NO-21-24VAC-DC
118700
Y7-118700
EATON - MOELLER
1 Pcs.
Automation > Device for monitoring of safety-related circuits
Relay timers (KETR, KEMR, KESR)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller ESR5-NO-21-24VAC-DC safety relay emergency stop/protective door is deployed in industrial automation systems to manage safety circuits associated with emergency stops and protective interlocking. Devices of this type continuously monitor input signals from safety sensors and swiftly interrupt power to hazardous machine elements when a fault or trip condition is detected. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Model (EF000010): Basic device
- Suitable for rail mounting (EF003972): true
- With detachable clamps (EF003340): true
- Type of electric connection (EF003961): Screw connection
- Voltage type (supply voltage) (EF002991): AC/DC
- Supply voltage AC 50 Hz (EF007532): 24 V
- Supply voltage AC 60 Hz (EF007533): 24 V
- Supply voltage DC (EF007534): 24 V
- Suitable for monitoring of position switches (EF007270): true
- Suitable for monitoring of valves (EF007272): false
- Suitable for monitoring of tactile sensors (EF007271): false
- Suitable for monitoring of magnetic switches (EF007266): false
- Suitable for monitoring of proximity switches (EF007267): false
- Evaluation inputs (EF008245): 1-channel
- Power consumption (EF000346): 5.16 W
- With start input (EF003342): true
More info
▲General specifications
UL
UL 508
IEC/EN 60204
UL report applies to both US and Canada
UL File No.: E29184
Certified by UL for use in Canada
CSA-C22.2 No. 14-95
EN 50178
CE
IEC 62061
2014/30/EU
CSA Class No.: 3211-83; 3211-03
EN ISO 13849-1
UL Category Control No.: NKCR; NKCR7
Machines 2006/42/EG
Feature & Functions
Reinforced insulation
Safe insulation
Automatic reset
Approval for TÜV
Detachable clamps
Feedback circuit
Start input
2-channel
Contacts: silver tin oxide, gold plated (AgSnO2, 0.2 µm Au)
General information
65 mA, DC
Terminals: IP20
Enclosure: IP20
IP20
According to EN-61000-6-2
Top-hat rail fixing (according to IEC/EN 60715, 35 mm)
SIL 3, Safety integrity level, In accordance with IEC 61508
Cat. 4, Category
SILCL 3, Safety integrity level claim limit
5.05 x 10-10, PFHd, Probability of failure per hour
Safety relay for monitoring emergency stop and protective door switch
Monitoring of emergency-stop circuits
Module used to safely interrupt electrical circuits
Ambient conditions, mechanical
66 Months (Low Demand)
4 A at 360 O/h, DC-13 at 24 V, Outputs
2.5 A at 3600 O/h, DC-13 at 24 V, Outputs
0.4 W
In accordance with IEC 60947-5-1, Outputs
4 A at 360 O/h, AC-15 at 230 V, Outputs
Climatic environmental conditions
Cold to EN 60068-2-1
Damp heat, constant, to IEC 60068-2-3
Condensation: Non-condensing
Terminal capacities
2 x (0.2 – 1) mm², solid
1 x (0.2 – 2.5) mm², solid
2 x (0.25 – 1) mm², flexible with ferrule
1 x (0.25 – 2.5) mm², flexible with ferrule
0.6 x 3.5 mm, Terminal screws
Electrical rating
3.4 W (AC operated 50/60 Hz)
230 V AC
24 V AC/DC (power supply)
Fuse 6 A gL/gG, For output circuits, External
10A gL/gG, NEOZED (N/O), Output fuse, External, Output data
Input/Output
1500 VA, max., resistive load (τ = 0 ms), at 250 V AC
35 W max., inductive load (τ = 40 ms), at 220 V DC
48 W max., inductive load (τ = 40 ms), at 24 V DC
288 W max., resistive load (τ = 0 ms), at 48 V DC
35 W max., inductive load (τ = 40 ms), at 110 V DC
40 W max., inductive load (τ = 40 ms), at 48 V DC
77 W max., resistive load (τ = 0 ms), at 110 V DC
88 W max., resistive load (τ = 0 ms), at 220 V DC
100 ms typ. (K1, K2 - for UN automatic mode)
45 ms (single-channel)
6 A N/C, Limiting continuous current