View larger
S811+T30V3S 168992 Y7-168992 EATON ELECTRIC Soft starter, 304 A, 200 690 V AC, Us 24 V DC, with control unit..
S811+T30V3S
168992
Y7-168992
EATON - MOELLER
1 Pcs.
Automation > Soft starter
High Performance Soft Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Equipped with an integrated control unit, the Eaton Moeller S811+T30V3S soft starter regulates heavy-duty motor acceleration and deceleration to protect industrial infrastructure. Facilities rely on this high-capacity controller for safe and efficient management of large three-phase drives. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated operation current Ie at 40 °C Tu (EF007039): 304 A
- Rated operating voltage Ue (EF002418): 200 V
- Rated power three-phase motor, inline, at 230 V (EF007053): 90 kW
- Rated power three-phase motor, inline, at 400 V (EF007054): 160 kW
- Function (EF000030): Single direction
- Internal bypass (EF009214): Yes
- With display (EF000458): Yes
- Torque control (EF009215): No
- Rated surrounding temperature without derating (EF007074): 50 °C
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 24 V
- Voltage type for actuating (EF008242): DC
- Integrated motor overload protection (EF007297): Yes
- Release class (EF006668): Adjustable
- Degree of protection (IP) (EF005474): IP20
More info
▲General specifications
C-Tick
CSA
UL File No.: E202571
UL Category Control No.: NMFT
GB14048
CSA22.2-14-1995
IEC/EN 60947-4-2
UL
CE
UL 508
Features & Functions
Internal bypass
Internal bypass contacts
Motor overload protection
Soft start function
Overload monitoring
Min. ramp time 1 s - fast switching (semiconductor contactor)
Current limitation
Single direction
Suppression of closing transients
Potential isolation between power and control sections
Underload monitoring
General
NEMA Other
CLASS 10 (star-delta replacement)
CLASS 20 (heavy starting duty 3 x Iₑ for 45 s)
Climatic environmental conditions
Max. 2000 m
Damp heat, cyclic, to IEC 60068-2-30
Main conducting paths
Motor rating
Terminal capacities
1 x (2.5 - 4) mm², Control circuit cables
1 x (70 - 240) mm², Main cables
2 x (25 - 240) mm², Main cables
1 x (70 - 240) mm², Main cables
1 x (2.5 - 4) mm², Control circuit cables
2 x (25 - 240) mm², Main cables
2 x (4 - 500 kcmil), Main cables
1 x (14 - 12), Control circuit cables
1 x (4 - 500 kcmil), Main cables
2 x (1 - 2.5) mm², Control circuit cables
2 x (25 - 240) mm², Main cables
1 x (70 - 240) mm², Main cables
4 mm Hexagon socket-head screw, Terminal screw, Main cables
28.3 Nm (> 150 mm²)
25.5 Nm (≤ 150 mm²)
Control circuit
10 A/150 ms, Control circuit, Regulator supply at peak performance (close bypass) at 24 V DC
1000 mA, Control circuit, Regulator supply
100 mA, Control circuit, Digital inputs, External 24 V (no-load)
Input/Output
24 V DC
Soft start function
100% (Kickstart voltage)