View larger
PFIM-80/4/03-MW 235420 Y7-235420 EATON ELECTRIC Residual current circuit breaker (RCCB), 80A, 4p, 300mA, typ..
PFIM-80/4/03-MW
PFIM-80/4/03-MW
Y7-235420
EATON - MOELLER
1 unit
Automation > Residual current circuit breaker (RCCB)
Modular Switchgear – Industrial
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Providing dependable safety in commercial and industrial power networks, the Eaton Moeller PFIM-80/4/03-MW residual current circuit breaker detects harmful current leakage and promptly isolates the affected circuit.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of poles: 4
- Rated voltage: 400 V
- Rated current: 80 A
- Rated fault current: 0.3 A
- Rated insulation voltage Ui: 440 V
- Rated impulse withstand voltage Uimp: 4 kV
- Power loss: 11.4 W
- Mounting method: DIN rail
- Leakage current type: AC
- Selective protection: No
- Short-time delayed tripping: No
- Short-circuit breaking capacity (Icw): 10 kA
- Surge current capacity: 0.25 kA
- Voltage type: AC
- With interlocking device: Yes
- Frequency: 50 Hz
More info
▲General specifications
| Product Name | Eaton Moeller series xPole - PFIM Type AC, A, U, R RCCB |
| Catalog Number | 235420 |
| Model Code | PFIM-80/4/03-MW |
| EAN | 4015082354206 |
| Product Length/Depth | 76 mm |
| Product Height | 80 mm |
| Product Width | 70 mm |
| Product Weight | 0.377 kg |
| Compliances | RoHS conform |
| Certifications | IEC/EN 61008 |
Delivery program
| Application |
|
| Number of poles | Four-pole |
| Tripping time | Non-delayed |
| Amperage Rating | 80 A |
| Rated short-circuit strength | 10 kA |
| Fault current rating | 300 mA |
| Sensitivity type | AC current sensitive |
| Impulse withstand current | Partly surge-proof 250 A |
| Type |
|
Technical Data - Electrical
| Voltage rating | 230 V AC / 400 V AC |
| Rated operational voltage (Ue) - max | 400 V |
| Rated insulation voltage (Ui) | 440 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Rated fault current - min | 0.3 A |
| Rated fault current - max | 0.3 A |
| Frequency rating | 50 Hz |
| Short-circuit rating | 80 A (max. admissible back-up fuse) |
| Leakage current type | AC |
| Rated residual making and breaking capacity | 800 A |
| Admissible back-up fuse overload - max | 50 A gG/gL |
| Rated short-time withstand current (Icw) | 10 kA |
| Surge current capacity | 0.25 kA |
| Test circuit range | 196 V AC - 456 V AC |
| Pollution degree | 2 |
| Lifespan, electrical | 4000 operations |
Technical Data - Mechanical
| Frame | 45 mm |
| Width in number of modular spacings | 4 |
| Built-in width (number of units) | 70 mm (4 SU) |
| Built-in depth | 70.5 mm |
| Mounting Method | DIN rail Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715 |
| Degree of protection | IP20, IP40 with suitable enclosure IP20 |
| Terminals (top and bottom) | Open mouthed/lift terminals |
| Terminal capacity (solid wire) | 1.5 mm² - 35 mm² |
| Connectable conductor cross section (solid-core) - min | 1.5 mm² |
| Connectable conductor cross section (solid-core) - max | 35 mm² |
| Terminal capacity (stranded cable) | 16 mm² (2x) |
| Connectable conductor cross section (multi-wired) - min | 1.5 mm² |
| Connectable conductor cross section (multi-wired) - max | 16 mm² |
| Terminal protection | Finger and hand touch safe, DGUV VS3, EN 50274 |
| Busbar material thickness | 0.8 mm - 2 mm |
| Lifespan, mechanical | 20000 operations |
| Permitted storage and transport temperature - min | -35 °C |
| Permitted storage and transport temperature - max | 60 °C |
| Climatic proofing | 25-55 °C / 90-95% relative humidity according to IEC 60068-2 |
Design verification as per IEC/EN 61439 - technical data
| Rated operational current for specified heat dissipation (In) | 80 A |
| Heat dissipation per pole, current-dependent | 0 W |
| Equipment heat dissipation, current-dependent | 11.4 W |
| Static heat dissipation, non-current-dependent | 0 W |
| Heat dissipation capacity | 0 W |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature - max | 60 °C |
Design verification as per IEC/EN 61439
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Additional information
| Accessories required | Z-HK 248432 |
| Features | Additional equipment possible Residual current circuit breaker |
| Fitted with: | Interlocking device |
| Special features |
|
| Used with | Type AC PFIM Residual current circuit breakers KLV-TC-4 276241 (Compact enclosure) Z-FW/LP 248296 (Remote control and automatic switching device) Z-RC/AK-4MU 101062 (sealing cover set) |