View larger
PFIM-63/2/003-MW
235398
Y7-235398
EATON - MOELLER
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Product Name | Eaton Moeller series xPole - PFIM Type AC, A, U, R RCCB |
| Catalog Number | 235398 |
| Model Code | PFIM-63/2/003-MW |
| EAN | 4015082353988 |
| Product Length/Depth | 76 mm |
| Product Height | 80 mm |
| Product Width | 35 mm |
| Product Weight | 0.21 kg |
| Compliances | RoHS conform |
| Certifications | IEC/EN 61008 |
| Application |
|
| Number of poles | Two-pole |
| Tripping time | Non-delayed |
| Amperage Rating | 63 A |
| Rated short-circuit strength | 10 kA |
| Fault current rating | 30 mA |
| Sensitivity type | AC current sensitive |
| Impulse withstand current | Partly surge-proof 250 A |
| Type |
|
| Voltage rating | 230 V AC |
| Rated operational voltage (Ue) - max | 230 V |
| Rated insulation voltage (Ui) | 440 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Rated fault current - min | 0.03 A |
| Rated fault current - max | 0.03 A |
| Frequency rating | 50 Hz |
| Short-circuit rating | 63 A (max. admissible back-up fuse) |
| Leakage current type | AC |
| Rated residual making and breaking capacity | 630 A |
| Admissible back-up fuse overload - max | 40 A gG/gL |
| Rated short-time withstand current (Icw) | 10 kA |
| Surge current capacity | 0.25 kA |
| Test circuit range | 196 V AC - 264 V AC |
| Pollution degree | 2 |
| Lifespan, electrical | 4000 operations |
| Frame | 45 mm |
| Width in number of modular spacings | 2 |
| Built-in width (number of units) | 35 mm (2 SU) |
| Built-in depth | 70.5 mm |
| Mounting Method | Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715 DIN rail |
| Degree of protection | IP20 IP20, IP40 with suitable enclosure |
| Terminals (top and bottom) | Open mouthed/lift terminals |
| Terminal capacity (solid wire) | 1.5 mm² - 35 mm² |
| Connectable conductor cross section (solid-core) - min | 1.5 mm² |
| Connectable conductor cross section (solid-core) - max | 35 mm² |
| Terminal capacity (stranded cable) | 16 mm² (2x) |
| Connectable conductor cross section (multi-wired) - min | 1.5 mm² |
| Connectable conductor cross section (multi-wired) - max | 16 mm² |
| Terminal protection | Finger and hand touch safe, DGUV VS3, EN 50274 |
| Busbar material thickness | 0.8 mm - 2 mm |
| Lifespan, mechanical | 20000 operations |
| Permitted storage and transport temperature - min | -35 °C |
| Permitted storage and transport temperature - max | 60 °C |
| Climatic proofing | 25-55 °C / 90-95% relative humidity according to IEC 60068-2 |
| Rated operational current for specified heat dissipation (In) | 63 A |
| Heat dissipation per pole, current-dependent | 0 W |
| Equipment heat dissipation, current-dependent | 9.7 W |
| Static heat dissipation, non-current-dependent | 0 W |
| Heat dissipation capacity | 0 W |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature - max | 60 °C |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
| Accessories required | Z-HK 248432 |
| Features | Residual current circuit breaker Additional equipment possible |
| Fitted with: | Interlocking device |
| Special features |
|
| Used with | Type AC PFIM Residual current circuit breakers KLV-TC-2 276240 (Compact enclosure) Z-FW/LP 248296 (Remote control and automatic switching device) Z-RC/AK-2MU 285385 (sealing cover set) |
| Feature Name | Feature Value |
|---|---|
| Number of poles (EF001391) | 2 |
| Rated voltage (EF000228) | 230 V |
| Rated current (EF000227) | 63 A |
| Rated fault current (EF002358) | 0.03 A |
| Rated insulation voltage Ui (EF001366) | 440 V |
| Rated impulse withstand voltage Uimp (EF011980) | 4 kV |
| Power loss (EF005387) | 9.7 W |
| Mounting method (EF000003) | DIN rail |
| Leakage current type (EF002560) | AC |
| Selective protection (EF002561) | No |
| Short-time delayed tripping (EF003604) | No |
| Short-circuit breaking capacity (Icw) (EF002562) | 10 kA |
| Surge current capacity (EF002564) | 0.25 kA |
| Voltage type (EF000187) | AC |
| With interlocking device (EF007385) | Yes |
| Frequency (EF005455) | 50 Hz |
| Additional equipment possible (EF008148) | Yes |
| Degree of protection (IP) (EF005474) | IP20 |
| Width in number of modular spacings (EF002950) | 2 |
| Built-in depth (EF000218) | 70.5 mm |
| Ambient temperature during operating (EF007515) | -25 °C |
| Pollution degree (EF002570) | 2 |
| Connectable conductor cross section multi-wired (EF007343) | 1.5 mm² |
| Connectable conductor cross section solid-core (EF007337) | 1.5 mm² |
| RAL-number (similar) (EF003882) | 7035 |
| Explosion-proof (EF004663) | No |