View larger
PFIM-40/4/003-G-MW 235453 Y7-235453 EATON ELECTRIC Residual current circuit breaker (RCCB), 40A, 4p, 30mA, t..
PFIM-40/4/003-G-MW
235453
Y7-235453
EATON - MOELLER
1 Pcs.
Automation > Residual current circuit breaker (RCCB)
Modular Switchgear – Tertiary and Differential
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for industrial and commercial distribution panels, this Eaton Moeller PFIM-40/4/003-G-MW 235453 residual current circuit breaker (RCCB) safeguards personnel and machinery by detecting earth fault currents. Safety devices of this type interrupt power supplies instantly when insulation failures create dangerous leakage paths.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of poles (EF001391): 4
- Rated voltage (EF000228): 400 V
- Rated current (EF000227): 40 A
- Rated fault current (EF002358): 0.03 A
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Mounting method (EF000003): DIN rail
- Leakage current type (EF002560): AC
- Selective protection (EF002561): No
- Short-time delayed tripping (EF003604): Yes
- Short-circuit breaking capacity (Icw) (EF002562): 10 kA
- Surge current capacity (EF002564): 3 kA
- Voltage type (EF000187): AC
- With interlocking device (EF007385): Yes
- Frequency (EF005455): 50 Hz
- Additional equipment possible (EF008148): Yes
More info
▲General specifications
Delivery program
- PFIM
- Residual current circuit breakers
- Type G (ÖVE E 8601)
Technical data - electrical
Technical data - mechanical
DIN rail
IP20, IP40 with suitable enclosure
Design verification as per IEC/EN 61439 - technical data
Design verification as per IEC/EN 61439
Additional information
Residual current circuit breaker
- Maximum operating temperature is 60 °C: Starting at 40 °C, the max. permissible continuous current decreases by 2.5% for every 1 °C
- Tripping signal contact for subsequent installation Z-NHK 248434
Z-FW/LP 248296 (Remote control and automatic switching device)
Z-RC/AK-4MU 101062 (sealing cover set)