View larger
PFIM-40/4/003-MW 235410 Y7-235410 EATON ELECTRIC Residual current circuit breaker (RCCB), 40A, 4p, 30mA, typ..
PFIM-40/4/003-MW
235410
Y7-235410
EATON - MOELLER
1 Pcs.
Automation > Residual current circuit breaker (RCCB)
Modular Switchgear - Differential
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for installation in electrical switchgear, a PFIM-40/4/003-MW 235410 Y7-235410 EATON ELECTRIC Residual current circuit breaker (RCCB), 40A, 4p, 30mA, typ.. protects systems and users from dangerous earth fault currents. It functions by disconnecting the electricity supply the moment a leakage current is identified in the protected network.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Name: Eaton Moeller series xPole - PFIM Type AC, A, U, R RCCB
- Catalog Number: 235410
- Model Code: PFIM-40/4/003-MW
- EAN: 4015082354107
- Product Length/Depth: 76 mm
- Product Height: 80 mm
- Product Width: 70 mm
- Product Weight: 0.318 kg
- Compliances: RoHS conform
- Certifications: IEC/EN 61008
- Number of poles: Four-pole
- Tripping time: Non-delayed
- Amperage Rating: 40 A
- Rated short-circuit strength: 10 kA
- Fault current rating: 30 mA
- Sensitivity type: AC current sensitive
More info
▲General specifications
| Product Name | Eaton Moeller series xPole - PFIM Type AC, A, U, R RCCB |
| Catalog Number | 235410 |
| Model Code | PFIM-40/4/003-MW |
| EAN | 4015082354107 |
| Product Length/Depth | 76 mm |
| Product Height | 80 mm |
| Product Width | 70 mm |
| Product Weight | 0.318 kg |
| Compliances | RoHS conform |
| Certifications | IEC/EN 61008 |
Delivery program
| Application |
|
| Number of poles | Four-pole |
| Tripping time | Non-delayed |
| Amperage Rating | 40 A |
| Rated short-circuit strength | 10 kA |
| Fault current rating | 30 mA |
| Sensitivity type | AC current sensitive |
| Impulse withstand current | Partly surge-proof 250 A |
| Type |
|
Technical Data - Electrical
| Voltage rating | 230 V AC / 400 V AC |
| Rated operational voltage (Ue) - max | 400 V |
| Rated insulation voltage (Ui) | 440 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Rated fault current - min | 0.03 A |
| Rated fault current - max | 0.03 A |
| Frequency rating | 50 Hz |
| Short-circuit rating | 63 A (max. admissible back-up fuse) |
| Leakage current type | AC |
| Rated residual making and breaking capacity | 500 A |
| Admissible back-up fuse overload - max | 25 A gG/gL |
| Rated short-time withstand current (Icw) | 10 kA |
| Surge current capacity | 0.25 kA |
| Test circuit range | 196 V AC - 264 V AC |
| Pollution degree | 2 |
| Lifespan, electrical | 4000 operations |
Technical Data - Mechanical
| Frame | 45 mm |
| Width in number of modular spacings | 4 |
| Built-in width (number of units) | 70 mm (4 SU) |
| Built-in depth | 70.5 mm |
| Mounting Method | DIN rail Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715 |
| Degree of protection | IP20, IP40 with suitable enclosure IP20 |
| Terminals (top and bottom) | Open mouthed/lift terminals |
| Terminal capacity (solid wire) | 1.5 mm² - 35 mm² |
| Connectable conductor cross section (solid-core) - min | 1.5 mm² |
| Connectable conductor cross section (solid-core) - max | 35 mm² |
| Terminal capacity (stranded cable) | 16 mm² (2x) |
| Connectable conductor cross section (multi-wired) - min | 1.5 mm² |
| Connectable conductor cross section (multi-wired) - max | 16 mm² |
| Terminal protection | Finger and hand touch safe, DGUV VS3, EN 50274 |
| Busbar material thickness | 0.8 mm - 2 mm |
| Lifespan, mechanical | 20000 operations |
| Permitted storage and transport temperature - min | -35 °C |
| Permitted storage and transport temperature - max | 60 °C |
| Climatic proofing | 25-55 °C / 90-95% relative humidity according to IEC 60068-2 |
Design verification as per IEC/EN 61439 - technical data
| Rated operational current for specified heat dissipation (In) | 40 A |
| Heat dissipation per pole, current-dependent | 0 W |
| Equipment heat dissipation, current-dependent | 13.1 W |
| Static heat dissipation, non-current-dependent | 0 W |
| Heat dissipation capacity | 0 W |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature - max | 60 °C |
Design verification as per IEC/EN 61439
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Additional information
| Accessories required | Z-HK 248432 |
| Features | Additional equipment possible Residual current circuit breaker |
| Fitted with: | Interlocking device |
| Special features |
|
| Used with | Residual current circuit breakers Type AC PFIM KLV-TC-4 276241 (Compact enclosure) Z-FW/LP 248296 (Remote control and automatic switching device) Z-RC/AK-4MU 101062 (sealing cover set) |