View larger
PFIM-63/4/01-U 235746 FRCMM-16/4/01-U EATON ELECTRIC Residual current circuit-breaker, 63A, 4pole, 100mA, ty..
PFIM-63/4/01-U
235746
FRCMM-16/4/01-U
EATON - MOELLER
1 Pcs.
Automation > Residual current circuit breaker (RCCB)
Modular Switchgear – Tertiary and Differential
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A residual current circuit-breaker monitors phase imbalances to detect insulation failures and automatically disconnects the supply to prevent electrical hazards. These units form the backbone of safety infrastructure in commercial buildings and industrial control panels.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of poles (EF001391): 4
- Rated voltage (EF000228): 400 V
- Rated current (EF000227): 63 A
- Rated fault current (EF002358): 0.1 A
- Rated insulation voltage Ui (EF001366): 440 V
- Rated impulse withstand voltage Uimp (EF011980): 4 kV
- Mounting method (EF000003): DIN rail
- Selective protection (EF002561): Yes
- Short-time delayed tripping (EF003604): No
- Short-circuit breaking capacity (Icw) (EF002562): 10 kA
- Surge current capacity (EF002564): 5 kA
- Voltage type (EF000187): AC
- With interlocking device (EF007385): Yes
- Frequency (EF005455): 50 Hz
- Additional equipment possible (EF008148): Yes
- Degree of protection (IP) (EF005474): IP20
More info
▲General specifications
Delivery program
Technical data - electrical
Technical data - mechanical
Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
IP20
Design verification as per IEC/EN 61439 - technical data
Design verification as per IEC/EN 61439
Additional information
Selective protection
Additional equipment possible
- Maximum operating temperature is 60 °C: Starting at 40 °C, the max. permissible continuous current decreases by 1.8% for every 1 °C
- Tripping signal contact for subsequent installation Z-NHK 248434
Z-FW/LP 248296 (Remote control and automatic switching device)
Z-RC/AK-4MU 101062 (sealing cover set)