EATON - MOELLER PFR2-03-S/A PFR2-03-S/A 235864 Y7-235864 EATON ELECTRIC Residual current circuit-breaker, 25A, 0p, 3mA, A-Char View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PFR2-03-S/A 235864 Y7-235864 EATON ELECTRIC Residual current circuit-breaker, 25A, 0p, 3mA, A-Char

PFR2-03-S/A

235864

Y7-235864

EATON - MOELLER

1 Pcs.

Residual current circuit-breaker, 25A, 0p, 3mA, A-Char PFR2-03-S/A Eaton Distribution parts. Residual current circuit-breaker, 25A, 0p, 3mA, A-Char, 2 Specially matched residual current relay and ring-type transformer, rated fault currents 0.3 A and 1 A, standard (-S/A) and sensitive and selective (-U) type, auxiliary contact for fitting to at a later time, temperature range, suitable for outdoor use (on-site power and outdoor distribution board) up to -25 °C

Automation > Residual current circuit breaker (RCCB)
Modular Switchgear – Industrial

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton Distribution parts
Catalog Number
235864
Model Code
PFR2-03-S/A
EAN
4015082358648
Product Length/Depth
80 mm
Product Height
76 mm
Product Width
70 mm
Product Weight
0.296 kg
Compliances
RoHS conform

Product specifications

Used with
KLV-TC-4 276241 (Compact enclosure)Z-RC/AK-4TE 101062 (sealing cover set)
PFR2
Residual current relay
Type S/A
KLV-TC-4 276241 (Compact enclosure)
Z-RC/AK-4TE 101062 (sealing cover set)
Type
Special features
  • Ambient temperature hint: Starting at 40 °C, the max. permissible continuous current decreases by 3% for every 1 °C
  • Tripping signal contact for subsequent installation Z-NHK 248434
Amperage Rating
25 A
Voltage rating
230 V AC / 400 V AC
Features
Residual current relay
Additional equipment possible
Selective protection
Accessories required
Z-HK 248432
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Frame
45 mm
Frequency rating
50 Hz
Pollution degree
2
Mounting Method
Quick attachment with 2 latch positions on top-hat rail IEC/EN 60715
DIN rail
Climatic proofing
25-55 °C / 90-95% relative humidity according to IEC 60068-2
Rated impulse withstand voltage (Uimp)
4 kV
Rated short-time withstand current (Icw)
10 kA
Built-in width (number of units)
70 mm (4 SU)
Busbar material thickness
0.8 mm - 2 mm
Terminal protection
Finger and hand touch safe, DGUV VS3, EN 50274
Terminals (top and bottom)
Twin-purpose terminals
Test circuit range
184 V AC - 440 V AC
Ambient operating temperature - max
60 °C
Ambient operating temperature - min
-25 °C
Built-in depth
69.5 mm
Connectable conductor cross section (multi-wired) - max
16 mm²
Connectable conductor cross section (multi-wired) - min
1.5 mm²
Connectable conductor cross section (solid-core) - max
35 mm²
Connectable conductor cross section (solid-core) - min
1.5 mm²
Fault current rating
300 mA
Heat dissipation capacity
0 W
Heat dissipation per pole, current-dependent
0 W
Permitted storage and transport temperature - max
60 °C
Permitted storage and transport temperature - min
-35 °C
Lifespan, mechanical
20000 operations
Degree of protection
IP20
IP20, IP40 with suitable enclosure
Number of poles
Four-pole
Leakage current type
A
Lifespan, electrical
4000 operations
Sensitivity type
Pulse-current sensitive
Rated fault current - max
0.3 A
Rated fault current - min
0.3 A
Rated insulation voltage (Ui)
440 V
Rated operational current for specified heat dissipation (In)
25 A
Rated operational voltage (Ue) - max
400 V
Surge current capacity
5 kA
Width in number of modular spacings
4
Voltage type
AC
Terminal capacity (solid wire)
1.5 mm² - 35 mm²
Tripping time
40 ms delayed - selective switch off
Rated short-circuit strength
5 kA
Terminal capacity (stranded cable)
16 mm² (2x)
RAL-number
7035

ETIM for 235864 Circuit breakers and fuses (EC000003)
Feature Name Feature Value
Number of poles (EF001391) 4
Rated voltage (EF000228) 400 V
Rated current (EF000227) 25 A
Rated fault current (EF002358) 0.3 A
Rated insulation voltage Ui (EF001366) 440 V
Rated impulse withstand voltage Uimp (EF011980) 4 kV
Mounting method (EF000003) DIN rail
Leakage current type (EF002560) A
Selective protection (EF002561) Yes
Short-time delayed tripping (EF003604) No
Short-circuit breaking capacity (Icw) (EF002562) 10 kA
Surge current capacity (EF002564) 5 kA
Voltage type (EF000187) AC
With interlocking device (EF007385) No
Frequency (EF005455) 50 Hz
Additional equipment possible (EF008148) Yes
Degree of protection (IP) (EF005474) IP20
Width in number of modular spacings (EF002950) 4
Built-in depth (EF000218) 69.5 mm
Ambient temperature during operating (EF007515) -25 °C
Pollution degree (EF002570) 2
Connectable conductor cross section multi-wired (EF007343) 1.5 mm²
Connectable conductor cross section solid-core (EF007337) 1.5 mm²
RAL-number (similar) (EF003882) 7035
Explosion-proof (EF004663) No

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.