View larger
RASP5-8420PNT-412R111S1 199056 Y7-199056 EATON ELECTRIC RASP5-8420PNT-412R111S1
RASP5-8420PNT-412R111S1
199056
Y7-199056
EATON - MOELLER
1 Pcs.
Automation > Frequency converter less than 1 kV
Rapid Link Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Rapid Link Speed controller RASP5-8420PNT-412R111S1 manages motor velocity and communication in distributed drive systems. Decentralized speed controllers provide local motor management while integrating seamlessly with broader industrial network protocols.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Name: Eaton Rapid Link Speed controller
- Catalog Number: 199056
- Model Code: RASP5-8420PNT-412R111S1
- EAN: 4015081971145
- Product Length/Depth: 195 mm
- Product Height: 270 mm
- Product Width: 220 mm
- Product Weight: 3.83 kg
- Certifications: IEC/EN 61800-5-1 RoHS UL 61800-5-1 CE UL approval
- Degree of protection: NEMA 12 IP65
- Electromagnetic compatibility: 1st and 2nd environments (according to EN 61800-3)
- Overvoltage category: III
- Product category: Speed controller
- Protocol: PROFINET IO
- Rated impulse withstand voltage (Uimp): 2000 V
More info
▲General specifications
| Product Name | Eaton Rapid Link Speed controller |
| Catalog Number | 199056 |
| Model Code | RASP5-8420PNT-412R111S1 |
| EAN | 4015081971145 |
| Product Length/Depth | 195 mm |
| Product Height | 270 mm |
| Product Width | 220 mm |
| Product Weight | 3.83 kg |
| Certifications | IEC/EN 61800-5-1 RoHS UL 61800-5-1 CE UL approval |
| Catalog Notes |
|
Features & Functions
| Features | Internal and on heat sink, temperature-controlled Fan Parameterization: drivesConnect mobile (App) Parameterization: Fieldbus Parameterization: drivesConnect Parameterization: Keypad |
| Fitted with: | Two sensor inputs through M12 sockets (max. 150 mA) for quick stop and interlocked manual operation Selector switch (Positions: REV - OFF - FWD) PTC thermistor monitoring Control unit 2 Actuator outputs Breaking resistance Key switch position AUTO Braking resistance Internal DC link Key switch position OFF/RESET Fan IGBT inverter Key switch position HAND PC connection Manual override switch Thermo-click with safe isolation |
| Functions | 3 fixed speeds 1 potentiometer speed Brake chopper with braking resistance for dynamic braking 4-quadrant operation possible STO (Safe Torque Off) |
General information
| Degree of protection | NEMA 12 IP65 |
| Electromagnetic compatibility | 1st and 2nd environments (according to EN 61800-3) |
| Overvoltage category | III |
| Product category | Speed controller |
| Product category | Speed controller |
| Protocol | PROFINET IO |
| Radio interference class | C1: for conducted emissions only C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary. |
| Rated impulse withstand voltage (Uimp) | 2000 V |
| System configuration type | Center-point earthed star network (TN-S network) AC voltage Phase-earthed AC supply systems are not permitted. |
Ambient conditions, mechanical
| Mounting position | Vertical |
| Shock resistance | 15 g, Mechanical, According to IEC/EN 60068-2-27, 11 ms, Half-sinusoidal shock 11 ms, 1000 shocks per shaft |
| Vibration | Resistance: 6 Hz, Amplitude 0.15 mm Resistance: According to IEC/EN 60068-2-6 Resistance: 57 Hz, Amplitude transition frequency on acceleration Resistance: 10 - 150 Hz, Oscillation frequency |
Climatic environmental conditions
| Altitude | Above 1000 m with 1 % performance reduction per 100 m Max. 2000 m |
| Ambient operating temperature - min | -10 °C |
| Ambient operating temperature - max | 40 °C |
| Ambient storage temperature - min | -40 °C |
| Ambient storage temperature - max | 70 °C |
| Climatic proofing | In accordance with IEC/EN 50178 < 95 %, no condensation |
Main circuit
| Current limitation | 0.8 - 8.5 A, motor, main circuit Adjustable, motor, main circuit |
| Delay time | < 10 ms, On-delay < 10 ms, Off-delay |
| Efficiency | 98 % (η) |
| Heat dissipation at current/speed | 51.6 W at 25% current and 0% speed 53.8 W at 25% current and 50% speed 60.9 W at 50% current and 0% speed 64 W at 50% current and 90% speed 65.4 W at 50% current and 50% speed 85.1 W at 100% current and 0% speed 94 W at 100% current and 50% speed 95.3 W at 100% current and 90% speed |
| Input current ILN at 150% overload | 7.8 A |
| Leakage current at ground IPE - max | 3.5 mA |
| Mains current distortion | 120 % |
| Mains switch-on frequency | Maximum of one time every 60 seconds |
| Mains voltage - max | 480 V |
| Mains voltage - min | 380 V |
| Mains voltage tolerance | 380 - 480 V (-10 %/+10 %, at 50/60 Hz) |
| Operating mode | PM and LSPM motors U/f control BLDC motors Synchronous reluctance motors Sensorless vector control (SLV) |
| Output frequency - max | 500 Hz |
| Output frequency - min | 0 Hz |
| Overload current | At 40 °C For 60 s every 600 s |
| Overload current IL at 150% overload | 12.7 A |
| Rated frequency - max | 66 Hz |
| Rated frequency - min | 45 Hz |
| Rated operational current (Ie) | 8.5 A at 150% overload (at an operating frequency of 8 kHz and an ambient air temperature of +40 °C) |
| Rated operational power at 380/400 V, 50 Hz, 3-phase | 4 kW |
| Rated operational voltage | 400 V AC, 3-phase 480 V AC, 3-phase |
| Resolution | 0.1 Hz (Frequency resolution, setpoint value) |
| Starting current - max | 200 %, IH, max. starting current (High Overload), For 2 seconds every 20 seconds, Power section |
| Supply frequency | 50/60 Hz |
| Switching frequency | 8 kHz, 4 - 32 kHz adjustable, fPWM, Power section, Main circuit |
Motor rating
| Assigned motor power at 460/480 V, 60 Hz, 3-phase | 5 HP |
Braking function
| Braking current | ≤ 0.6 A (max. 6 A for 120 ms), Actuator for external motor brake |
| Braking torque | Adjustable to 100 % (I/Ie), DC - Main circuit |
| Switch-on threshold for the braking transistor | 765 VDC |
Short-circuit rating
| Rated conditional short-circuit current (Iq) | 10 kA |
| Short-circuit protection (external output circuits) | Type 1 coordination via the power bus' feeder unit, Main circuit |
Control circuit
| Rated control voltage (Uc) | 24 V DC (-15 %/+20 %, external via AS-Interface® plug) |
Communication
| Communication interface | PROFINET, optional |
| Connection | Plug type: HAN Q4/2 |
| Interfaces | Number of slave addresses: 31 (AS-Interface®) Max. total power consumption from AS-Interface® power supply unit (30 V): 250 mA Specification: S-7.4 (AS-Interface®) |
Cable
| Cable length | C1 ≤ 1 m, maximum motor cable length C2 ≤ 5 m, maximum motor cable length C3 ≤ 25 m, maximum motor cable length |
Design verification
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |