View larger
RASP5-8402A31-4120101S1 198842 Y7-198842 EATON ELECTRIC RASP5-8402A31-4120101S1
RASP5-8402A31-4120101S1
198842
Y7-198842
EATON - MOELLER
1 Pcs.
Automation > Frequency converter less than 1 kV
Rapid Link Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller RASP5-8402A31-4120101S1 is a variable frequency drive utilized for precise motor speed regulation and process automation. In industrial automation, drives deliver efficient energy conversion and protect mechanical components by smoothing out startup currents.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Mains voltage (EF006780): 380 V
- Mains frequency (EF006783): 50/60 Hz
- Number of phases input (EF007117): 3
- Number of phases output (EF006998): 3
- Max. output frequency (EF007350): 500 Hz
- Max. output voltage (EF009560): 500 V
- Nominal output current I2N (EF009561): 8.5 A
- Power consumption (EF000346): 95 W
- Relative symmetric net frequency tolerance (EF007454): 10 %
- Relative symmetric net voltage tolerance (EF007453): 10 %
- Number of analogue outputs (EF001995): 0
- Number of analogue inputs (EF001994): 0
- Number of digital outputs (EF001993): 0
- Number of digital inputs (EF001992): 4
- With control element (EF001538): Yes
- Application in industrial area permitted (EF007294): Yes
More info
▲General specifications
UL 61800-5-1
RoHS
IEC/EN 61800-5-1
CE
Features & Functions
Diagnostics and reset on device and via AS-Interface
Parameterization: Fieldbus
Parameterization: drivesConnect mobile (App)
Parameterization: drivesConnect
Parameterization: Keypad
Control unit
Key switch position AUTO
Key switch position HAND
Thermo-click with safe isolation
PC connection
Selector switch (Positions: REV - OFF - FWD)
Internal DC link
Two sensor inputs through M12 sockets (max. 150 mA) for quick stop and interlocked manual operation
Key switch position OFF/RESET
Fan
IGBT inverter
Braking resistance
PTC thermistor monitoring
1 potentiometer speed
3 fixed speeds
Brake chopper with braking resistance for dynamic braking
For actuation of motors with mechanical brake
General
NEMA 12
ASI
C1: for conducted emissions only
AC voltage
Phase-earthed AC supply systems are not permitted.
Ambient conditions, mechanical
Resistance: According to IEC/EN 60068-2-6
Resistance: 6 Hz, Amplitude 0.15 mm
Resistance: 57 Hz, Amplitude transition frequency on acceleration
Climatic environmental conditions
Max. 2000 m
< 95 %, no condensation
Main circuit
0.8 - 8.5 A, motor, main circuit
< 10 ms, On-delay
Synchronous reluctance motors
Sensorless vector control (SLV)
BLDC motors
U/f control
At 40 °C
480 V AC, 3-phase
AC voltage
Phase-earthed AC supply systems are not permitted.
Motor rating
Braking function
Adjustable to 100 % (I/Ie), DC - Main circuit
Short-circuit rating
Control circuit
230/277 V AC (external brake 50/60 Hz)
Communication
Max. total power consumption from AS-Interface® power supply unit (30 V): 190 mA
Number of slave addresses: 31 (AS-Interface®)
Cable
C1 ≤ 1 m, maximum motor cable length
C2 ≤ 5 m, maximum motor cable length