Request QuoteProduct Overview
Eaton Moeller built the RASP5-5421PNT-412R000S1 frequency converter to manage motor speeds within complex automated systems and industrial manufacturing lines. Implementing adjustable frequency drives helps facility engineers optimize machine performance, reduce mechanical shock, and maintain strict process tolerances.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Mains voltage (EF006780): 380 V
- Mains frequency (EF006783): 50/60 Hz
- Number of phases input (EF007117): 3
- Number of phases output (EF006998): 3
- Max. output frequency (EF007350): 500 Hz
- Max. output voltage (EF009560): 500 V
- Nominal output current I2N (EF009561): 5.6 A
- Power consumption (EF000346): 58 W
- Relative symmetric net frequency tolerance (EF007454): 10 %
- Relative symmetric net voltage tolerance (EF007453): 10 %
- Number of analogue outputs (EF001995): 0
- Number of analogue inputs (EF001994): 0
- Number of digital outputs (EF001993): 2
- Number of digital inputs (EF001992): 4
- With control element (EF001538): Yes
- Application in industrial area permitted (EF007294): Yes
More info
▲General specifications
IEC/EN 61800-5-1
RoHS
UL approval
UL 61800-5-1
Features & Functions
Parameterization: drivesConnect
Parameterization: Keypad
Parameterization: drivesConnect mobile (App)
Two sensor inputs through M12 sockets (max. 150 mA) for quick stop and interlocked manual operation
2 Actuator outputs
Key switch position HAND
Control unit
Internal DC link
PTC thermistor monitoring
Manual override switch
Key switch position AUTO
Selector switch (Positions: REV - OFF - FWD)
Thermo-click with safe isolation
PC connection
IGBT inverter
3 fixed speeds
For actuation of motors with mechanical brake
General
NEMA 12
C1: for conducted emissions only
Phase-earthed AC supply systems are not permitted.
Center-point earthed star network (TN-S network)
Ambient conditions, mechanical
Resistance: 57 Hz, Amplitude transition frequency on acceleration
Resistance: According to IEC/EN 60068-2-6
Resistance: 10 - 150 Hz, Oscillation frequency
Climatic environmental conditions
Above 1000 m with 1 % performance reduction per 100 m
< 95 %, no condensation
Main circuit
Adjustable, motor, main circuit
< 10 ms, Off-delay
U/f control
BLDC motors
Synchronous reluctance motors
PM and LSPM motors
For 60 s every 600 s
480 V AC, 3-phase
Phase-earthed AC supply systems are not permitted.
Center-point earthed star network (TN-S network)
Motor rating
Braking function
≤ 30 % (I/Ie)
Short-circuit rating
Control circuit
180/207 V DC (external brake 50/60 Hz)
Communication
Specification: S-7.4 (AS-Interface®)
Number of slave addresses: 31 (AS-Interface®)
Cable
C1 ≤ 1 m, maximum motor cable length
C3 ≤ 25 m, maximum motor cable length