View larger
RASP5-5420PNT-4120110S1 199008 Y7-199008 EATON ELECTRIC RASP5-5420PNT-4120110S1
RASP5-5420PNT-4120110S1
199008
Y7-199008
EATON - MOELLER
1 Pcs.
Automation > Frequency converter less than 1 kV
Rapid Link Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller RASP5-5420PNT-4120110S1 operates as a robust decentralized drive solution designed to mount directly onto machine infrastructure for distributed motor control. Industrial facilities rely on such units to simplify complex wiring topologies while maintaining exact regulation over motor speeds and process variables. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Mains voltage (EF006780): 380 V
- Mains frequency (EF006783): 50/60 Hz
- Number of phases input (EF007117): 3
- Number of phases output (EF006998): 3
- Max. output frequency (EF007350): 500 Hz
- Max. output voltage (EF009560): 500 V
- Nominal output current I2N (EF009561): 5.6 A
- Power consumption (EF000346): 58 W
- Relative symmetric net frequency tolerance (EF007454): 10 %
- Relative symmetric net voltage tolerance (EF007453): 10 %
- Number of analogue outputs (EF001995): 0
- Number of analogue inputs (EF001994): 0
- Number of digital outputs (EF001993): 2
- Number of digital inputs (EF001992): 4
- With control element (EF001538): Yes
- Application in industrial area permitted (EF007294): Yes
More info
▲General specifications
IEC/EN 61800-5-1
UL 61800-5-1
UL approval
CE
Features & Functions
Parameterization: drivesConnect mobile (App)
Parameterization: Fieldbus
Parameterization: drivesConnect
Internal DC link
Key switch position OFF/RESET
PC connection
IGBT inverter
Braking resistance
2 Actuator outputs
Key switch position AUTO
Key switch position HAND
Selector switch (Positions: REV - OFF - FWD)
Two sensor inputs through M12 sockets (max. 150 mA) for quick stop and interlocked manual operation
PTC thermistor monitoring
Breaking resistance
Thermo-click with safe isolation
4-quadrant operation possible
3 fixed speeds
1 potentiometer speed
Brake chopper with braking resistance for dynamic braking
General
IP65
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Center-point earthed star network (TN-S network)
Phase-earthed AC supply systems are not permitted.
Ambient conditions, mechanical
Resistance: 57 Hz, Amplitude transition frequency on acceleration
Resistance: 6 Hz, Amplitude 0.15 mm
Resistance: According to IEC/EN 60068-2-6
Climatic environmental conditions
Above 1000 m with 1 % performance reduction per 100 m
< 95 %, no condensation
Main circuit
0.5 - 5.6 A, motor, main circuit
< 10 ms, On-delay
Sensorless vector control (SLV)
BLDC motors
PM and LSPM motors
U/f control
For 60 s every 600 s
480 V AC, 3-phase
Center-point earthed star network (TN-S network)
Phase-earthed AC supply systems are not permitted.
Motor rating
Braking function
Short-circuit rating
Control circuit
Communication
Specification: S-7.4 (AS-Interface®)
Number of slave addresses: 31 (AS-Interface®)
Cable
C3 ≤ 25 m, maximum motor cable length
C2 ≤ 5 m, maximum motor cable length