View larger
RASP5-4424EIP-412R000S1 198887 Y7-198887 EATON ELECTRIC RASP5-4424EIP-412R000S1
RASP5-4424EIP-412R000S1
198887
Y7-198887
EATON - MOELLER
1 Pcs.
Automation > Frequency converter less than 1 kV
Rapid Link Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Optimizing decentralized drive architectures is effortless with the Eaton Moeller RASP5-4424EIP-412R000S1, which integrates motor control and power electronics into a single robust enclosure. Such distributed frequency converters simplify machine wiring and allow close proximity mounting to pumps, fans, and material handling systems. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Mains voltage (EF006780): 380 V
- Mains frequency (EF006783): 50/60 Hz
- Number of phases input (EF007117): 3
- Number of phases output (EF006998): 3
- Max. output frequency (EF007350): 500 Hz
- Max. output voltage (EF009560): 500 V
- Nominal output current I2N (EF009561): 4.3 A
- Power consumption (EF000346): 46 W
- Relative symmetric net frequency tolerance (EF007454): 10 %
- Relative symmetric net voltage tolerance (EF007453): 10 %
- Number of analogue outputs (EF001995): 0
- Number of analogue inputs (EF001994): 0
- Number of digital outputs (EF001993): 2
- Number of digital inputs (EF001992): 4
- With control element (EF001538): Yes
- Application in industrial area permitted (EF007294): Yes
More info
▲General specifications
UL 61800-5-1
CE
UL approval
IEC/EN 61800-5-1
Features & Functions
Parameterization: drivesConnect
Parameterization: drivesConnect mobile (App)
Parameterization: Fieldbus
2 Actuator outputs
Key switch position AUTO
Thermo-click with safe isolation
Control unit
PC connection
Key switch position OFF/RESET
IGBT inverter
Key switch position HAND
Internal DC link
Manual override switch
Selector switch (Positions: REV - OFF - FWD)
PTC thermistor monitoring
3 fixed speeds
1 potentiometer speed
General
NEMA 12
C1: for conducted emissions only
Phase-earthed AC supply systems are not permitted.
Center-point earthed star network (TN-S network)
Ambient conditions, mechanical
Resistance: According to IEC/EN 60068-2-6
Resistance: 57 Hz, Amplitude transition frequency on acceleration
Resistance: 6 Hz, Amplitude 0.15 mm
Climatic environmental conditions
Max. 2000 m
< 95 %, no condensation
Main circuit
Adjustable, motor, main circuit
< 10 ms, On-delay
BLDC motors
PM and LSPM motors
U/f control
Sensorless vector control (SLV)
For 60 s every 600 s
480 V AC, 3-phase
Phase-earthed AC supply systems are not permitted.
Center-point earthed star network (TN-S network)
Motor rating
Braking function
≤ 30 % (I/Ie)
Short-circuit rating
Control circuit
400/480 V AC (external brake 50/60 Hz)
Communication
Specification: S-7.4 (AS-Interface®)
Number of slave addresses: 31 (AS-Interface®)
Cable
C2 ≤ 5 m, maximum motor cable length