View larger
RASP5-2402A31-5120100S1 198546 Y7-198546 EATON ELECTRIC RASP5-2402A31-5120100S1
RASP5-2402A31-5120100S1
198546
Y7-198546
EATON - MOELLER
1 Pcs.
Automation > Frequency converter less than 1 kV
Rapid Link Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for robust automation environments, the Eaton Moeller RASP5-2402A31-5120100S1 frequency converter provides accurate regulation for industrial electric drives. These devices are standard components in electrical engineering for matching motor speed profiles to precise operational requirements.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Mains voltage (EF006780): 380 V
- Mains frequency (EF006783): 50/60 Hz
- Number of phases input (EF007117): 3
- Number of phases output (EF006998): 3
- Max. output frequency (EF007350): 500 Hz
- Max. output voltage (EF009560): 500 V
- Nominal output current I2N (EF009561): 2.4 A
- Power consumption (EF000346): 32 W
- Relative symmetric net frequency tolerance (EF007454): 10 %
- Relative symmetric net voltage tolerance (EF007453): 10 %
- Number of analogue outputs (EF001995): 0
- Number of analogue inputs (EF001994): 0
- Number of digital outputs (EF001993): 0
- Number of digital inputs (EF001992): 4
- With control element (EF001538): Yes
- Application in industrial area permitted (EF007294): Yes
More info
▲General specifications
IEC/EN 61800-5-1
UL 61800-5-1
CE
UL approval
Features & Functions
Parameterization: Fieldbus
Parameterization: drivesConnect mobile (App)
Diagnostics and reset on device and via AS-Interface
Parameterization: Keypad
Two sensor inputs through M12 sockets (max. 150 mA) for quick stop and interlocked manual operation
PTC thermistor monitoring
Internal DC link
Key switch position AUTO
Key switch position HAND
Thermo-click with safe isolation
Control unit
PC connection
Four fixed speeds
Selector switch (Positions: REV - OFF - FWD)
Braking resistance
IGBT inverter
Breaking resistance
Brake chopper with braking resistance for dynamic braking
4-quadrant operation possible
General
NEMA 12
ASI
C2, C3: depending on the motor cable length, the connected load, and ambient conditions. External radio interference suppression filters (optional) may be necessary.
Center-point earthed star network (TN-S network)
AC voltage
Ambient conditions, mechanical
Resistance: According to IEC/EN 60068-2-6
Resistance: 57 Hz, Amplitude transition frequency on acceleration
Resistance: 6 Hz, Amplitude 0.15 mm
Climatic environmental conditions
Above 1000 m with 1 % performance reduction per 100 m
In accordance with IEC/EN 50178
Main circuit
0.2 - 2.4 A, motor, main circuit
< 10 ms, On-delay
U/f control
Synchronous reluctance motors
PM and LSPM motors
BLDC motors
At 40 °C
480 V AC, 3-phase
Center-point earthed star network (TN-S network)
AC voltage
Motor rating
Braking function
Adjustable to 100 % (I/Ie), DC - Main circuit
Short-circuit rating
Control circuit
24 V DC (-15 %/+20 %, external via AS-Interface® plug)
Communication
Specification: S-7.4 (AS-Interface®)
Max. total power consumption from AS-Interface® power supply unit (30 V): 190 mA
Cable
C1 ≤ 1 m, maximum motor cable length
C3 ≤ 25 m, maximum motor cable length