View larger
RAMO5-W420EIP-412RS1 199121 Y7-199121 EATON ELECTRIC RAMO5-W420EIP-412RS1
RAMO5-W420EIP-412RS1
199121
Y7-199121
EATON - MOELLER
1 Pcs.
Automation > Motor starter/Motor starter combination
Rapid Link Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Rapid Link reversing starter RAMO5-W420EIP-412RS1 from Eaton Moeller provides decentralized motor control and protection for distributed automation networks. Enclosed units of this type mount directly on machines to handle frequent switching cycles and reverse rotational direction close to the load.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Name: Eaton Rapid Link Reversing starter
- Catalog Number: 199121
- Model Code: RAMO5-W420EIP-412RS1
- EAN: 4015081971794
- Product Length/Depth: 120 mm
- Product Height: 270 mm
- Product Width: 220 mm
- Product Weight: 1.83 kg
- Certifications: RoHS CE CCC IEC/EN 60947-4-2 UL 60947-4-2 UL approval
- Functions: External reset possible Temperature compensated overload protection
- Class: CLASS 10 A
- Degree of protection: NEMA 12 IP65
- Electromagnetic compatibility: Class A
- Lifespan, electrical: 10,000,000 Operations (at AC-3)
- Lifespan, mechanical: 10,000,000 Operations (at AC-3)
- Model: Reversing starter
More info
▲General specifications
| Product Name | Eaton Rapid Link Reversing starter |
| Catalog Number | 199121 |
| Model Code | RAMO5-W420EIP-412RS1 |
| EAN | 4015081971794 |
| Product Length/Depth | 120 mm |
| Product Height | 270 mm |
| Product Width | 220 mm |
| Product Weight | 1.83 kg |
| Certifications | RoHS CE CCC IEC/EN 60947-4-2 UL 60947-4-2 UL approval |
| Catalog Notes | Assigned motor rating: for normal internally and externally ventilated 4 pole, three-phase asynchronous motors with 1500 rpm at 50 Hz or 1800 min at 60 Hz |
Features & Functions
| Features | Parameterization: drivesConnect Parameterization: Fieldbus Parameterization: Keypad Parameterization: drivesConnect mobile (App) |
| Fitted with: | Key switch position AUTO Thermo-click Key switch position OFF/RESET 2 Actuator outputs Electronic motor protection Key switch position HAND Two sensor inputs through M12 sockets (max. 150 mA) for quick stop and interlocked manual operation Manual override switch Thermistor monitoring PTC Short-circuit release |
| Functions | External reset possible Temperature compensated overload protection |
General information
| Class | CLASS 10 A |
| Degree of protection | NEMA 12 IP65 |
| Electromagnetic compatibility | Class A |
| Lifespan, electrical | 10,000,000 Operations (at AC-3) |
| Lifespan, mechanical | 10,000,000 Operations (at AC-3) |
| Model | Reversing starter |
| Overload release current setting - min | 0.3 A |
| Overload release current setting - max | 6.6 A |
| Overvoltage category | III |
| Product category | Motor starter |
| Product category | Motor starter |
| Protocol | EtherNet/IP |
| Rated impulse withstand voltage (Uimp) | 4000 V |
| System configuration type | Phase-earthed AC supply systems are not permitted. AC voltage Center-point earthed star network (TN-S network) |
| Type | Reversing starter |
| Voltage type | DC |
Ambient conditions, mechanical
| Mounting position | Vertical |
| Shock resistance | 15 g, Mechanical, According to IEC/EN 60068-2-27, 11 ms, Half-sinusoidal shock 11 ms, 1000 shocks per shaft |
| Vibration | Resistance: 10 - 150 Hz, Oscillation frequency Resistance: 57 Hz, Amplitude transition frequency on acceleration Resistance: 6 Hz, Amplitude 0.15 mm Resistance: According to IEC/EN 60068-2-6 |
Climatic environmental conditions
| Altitude | Max. 1000 m Max. 2000 m Above 1000 m with 1 % performance reduction per 100 m |
| Ambient operating temperature - min | -10 °C |
| Ambient operating temperature - max | 55 °C |
| Ambient storage temperature - min | -40 °C |
| Ambient storage temperature - max | 70 °C |
| Climatic proofing | < 95 %, no condensation In accordance with IEC/EN 50178 |
Main circuit
| Current limitation | 0.3 - 6.6 A, motor, main circuit Adjustable, motor, main circuit |
| Input current | 6.6 A (at 150 % Overload) |
| Mains switch-on frequency | Maximum of one time every 60 seconds |
| Mains voltage tolerance | 380 - 480 V (-15 %/+10 %, at 50/60 Hz) |
| Off-delay | 20 - 35 ms |
| On-delay | 20 - 35 ms |
| Output frequency | 50/60 Hz |
| Overload cycle | AC-53a |
| Rated frequency - max | 63 Hz |
| Rated frequency - min | 47 Hz |
| Rated operational current (Ie) | 6.6 A |
| Rated operational current (Ie) at 150% overload | 6.6 A |
| Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V | 6.6 A |
| Rated operational power at 380/400 V, 50 Hz - max | 3 kW |
| Rated operational power at 380/400 V, 50 Hz - min | 0.09 kW |
| Rated operational power at AC-3, 380/400 V, 50 Hz | 3 kW |
| Rated operational voltage | 480 V AC, 3-phase 400 V AC, 3-phase |
| Supply frequency | 50/60 Hz, fLN, Main circuit |
Motor rating
| Assigned motor power at 460/480 V, 60 Hz, 3-phase | 3 HP |
Short-circuit rating
| Rated conditional short-circuit current (Iq) | 10 kA |
| Short-circuit protection (external output circuits) | Type 1 coordination via the power bus' feeder unit, Main circuit |
Control circuit
| Rated control voltage (Uc) | 24 V DC (-15 %/+20 %, external via AS-Interface® plug) |
Communication
| Connection | Connections pluggable in power section |
Contacts
| Number of auxiliary contacts (normally closed contacts) | 0 |
| Number of auxiliary contacts (normally open contacts) | 2 |
Cable
| Cable length | 10 m, Radio interference level, maximum motor cable length |
Design verification
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |