Request QuoteProduct Overview
An Eaton Moeller RAMO5-W212A32-412RS1 reversing starter provides robust motor control and bi-directional switching capabilities for decentralized industrial automation architectures. Motor starters of this classification safely manage operational currents and protect connected mechanical loads against hazardous fault conditions. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Type of motor starter (EF009598): Reversing starter
- With short-circuit release (EF006691): Yes
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): DC
- Rated operation power at AC-3, 230 V, 3-phase (EF009599): 0 kW
- Rated operation power at AC-3, 400 V (EF001364): 3 kW
- Rated power, 460 V, 60 Hz, 3-phase (EF009600): 2.238 kW
- Rated power, 575 V, 60 Hz, 3-phase (EF009601): 0 kW
- Rated operation current Ie (EF001443): 6.6 A
- Rated operation current at AC-3, 400 V (EF009602): 6.6 A
- Overload release current setting (EF002336): 0.3 A
- Power consumption (EF000346): 8 W
- Ambient temperature, upper operating limit (EF009603): 55 °C
- Temperature compensated overload protection (EF009604): Yes
More info
▲General specifications
IEC/EN 60947-4-2
CCC
UL approval
CE
UL 60947-4-2
Features & Functions
Parameterization: drivesConnect
Diagnostics and reset on device and via AS-Interface
Parameterization: Keypad
Parameterization: Fieldbus
Manual override switch
1 Actuator output
Key switch position AUTO
Thermo-click
Electronic motor protection
Key switch position OFF/RESET
Thermistor monitoring PTC
Two sensor inputs through M12 sockets (max. 150 mA) for quick stop and interlocked manual operation
Short-circuit release
External reset possible
Temperature compensated overload protection
General
NEMA 12
ASI
AC voltage
Phase-earthed AC supply systems are not permitted.
Ambient conditions, mechanical
Resistance: 57 Hz, Amplitude transition frequency on acceleration
Resistance: According to IEC/EN 60068-2-6
Resistance: 6 Hz, Amplitude 0.15 mm
Climatic environmental conditions
Max. 1000 m
Above 1000 m with 1 % performance reduction per 100 m
In accordance with IEC/EN 50178
Main circuit
0.3 - 6.6 A, motor, main circuit
400 V AC, 3-phase
AC voltage
Phase-earthed AC supply systems are not permitted.
Motor rating
Braking function
Short-circuit rating
Control circuit
24 V DC (-15 %/+20 %, external via AS-Interface® plug)
Communication
Specification: S-7.A.E. (AS-Interface®)
Number of slave addresses: 62 (AS-Interface®)