View larger
RAMO5-D202A31-5120S1 198519 Y7-198519 EATON ELECTRIC RAMO5-D202A31-5120S1
RAMO5-D202A31-5120S1
198519
Y7-198519
EATON - MOELLER
1 Pcs.
Automation > Motor starter/Motor starter combination
Rapid Link Starters
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Eaton Moeller RAMO5-D202A31-5120S1 direct starter provides robust electronic motor control and integrated circuit protection for decentralized automation tasks. Motor starters of this classification ensure dependable switching and thermal defense for industrial drives in distributed plant networks.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of motor starter (EF009598): Direct starter
- With short-circuit release (EF006691): Yes
- Rated control supply voltage AC 50 Hz (EF003978): 0 V
- Rated control supply voltage AC 60 Hz (EF003979): 0 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): DC
- Rated operation power at AC-3, 230 V, 3-phase (EF009599): 0 kW
- Rated operation power at AC-3, 400 V (EF001364): 3 kW
- Rated power, 460 V, 60 Hz, 3-phase (EF009600): 2.238 kW
- Rated power, 575 V, 60 Hz, 3-phase (EF009601): 0 kW
- Rated operation current Ie (EF001443): 6.6 A
- Rated operation current at AC-3, 400 V (EF009602): 6.6 A
- Overload release current setting (EF002336): 0.3 A
- Power consumption (EF000346): 8 W
- Ambient temperature, upper operating limit (EF009603): 55 °C
- Temperature compensated overload protection (EF009604): Yes
More info
▲General specifications
CE
CCC
RoHS
IEC/EN 60947-4-2
UL 60947-4-2
Features & Functions
Diagnostics and reset on device and via AS-Interface
Parameterization: drivesConnect mobile (App)
Parameterization: Fieldbus
Parameterization: drivesConnect
Key switch position AUTO
Key switch position OFF/RESET
Key switch position HAND
Thermistor monitoring PTC
Thermo-click
Electronic motor protection
Two sensor inputs through M12 sockets (max. 150 mA) for quick stop and interlocked manual operation
External reset possible
For actuation of motors with mechanical brake
General
NEMA 12
AS-Interface profile cable: S-7.4 for 31 modules
Center-point earthed star network (TN-S network)
Phase-earthed AC supply systems are not permitted.
Ambient conditions, mechanical
Resistance: 6 Hz, Amplitude 0.15 mm
Resistance: According to IEC/EN 60068-2-6
Resistance: 10 - 150 Hz, Oscillation frequency
Climatic environmental conditions
Above 1000 m with 1 % performance reduction per 100 m
Max. 1000 m
< 95 %, no condensation
Main circuit
Adjustable, motor, main circuit
480 V AC, 3-phase
Center-point earthed star network (TN-S network)
Phase-earthed AC supply systems are not permitted.
Motor rating
Braking function
Short-circuit rating
Control circuit
24 V DC (-15 %/+20 %, external via AS-Interface® plug)
Communication
Number of slave addresses: 31 (AS-Interface®)
Specification: S-7.4 (AS-Interface®)