View larger
PXS24S-e16/F/ORT PXS24S16A002 EATON ELECTRIC Electronic overcurrent protection for 24V DC, fix 16A with trip..
PXS24S-e16/F/ORT
PXS24S16A002
PXS24S16A002
EATON - MOELLER
1 Pcs.
Automation > Current monitoring relay
Electronic overcurrent protection
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Electronic overcurrent protection device Eaton Moeller PXS24S-e16/F/ORT provides reliable circuit safeguarding in industrial automation environments. Devices of this type are routinely employed to monitor 24V DC power distribution lines, instantly interrupting current flow during overload conditions to prevent damage to sensitive downstream electronics and control hardware.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Name: Eaton Moeller series xEffect - PXS24 current monitoring relay
- Catalog Number: PXS24S16A002
- Model Code: PXS24S-e16/F/ORT
- EAN: 9010238011281
- UPC: 786689167592
- Product Length/Depth: 127 mm
- Product Height: 93 mm
- Product Width: 18 mm
- Product Weight: 0.118 kg
- Compliances: CE UL508 RoHS conform
- Certifications: EN45545-2 IEC 61373
- Type: Automation engineering 24V
- Amperage Rating: 16 A
- Voltage type: DC
- Voltage rating: 24 VDC (15 VDC - 30 VDC)
- Rated control supply voltage (Us) at AC, 50 Hz - min: 0 V
More info
▲General specifications
| Product Name | Eaton Moeller series xEffect - PXS24 current monitoring relay |
| Catalog Number | PXS24S16A002 |
| Model Code | PXS24S-e16/F/ORT |
| EAN | 9010238011281 |
| UPC | 786689167592 |
| Product Length/Depth | 127 mm |
| Product Height | 93 mm |
| Product Width | 18 mm |
| Product Weight | 0.118 kg |
| Compliances | CE UL508 RoHS conform |
| Certifications | EN45545-2 IEC 61373 |
Delivery program
| Type | Automation engineering 24V |
| Amperage Rating | 16 A |
Technical Data - Electrical
| Voltage type | DC |
| Voltage rating | 24 VDC (15 VDC - 30 VDC) |
| Rated control supply voltage (Us) at AC, 50 Hz - min | 0 V |
| Rated control supply voltage (Us) at AC, 50 Hz - max | 0 V |
| Rated control supply voltage (Us) at AC, 60 Hz - min | 0 V |
| Rated control supply voltage (Us) at AC, 60 Hz - max | 0 V |
| Rated control supply voltage (Us) at DC - min | 15 V |
| Rated control supply voltage (Us) at DC - max | 30 V |
| Rated operational current (Ie) fix | 16 A |
| Current measurement - min | 0 A |
| Current measurement - max | 20.8 A |
| Overload current and short-circuit current trip | Type 1.3 x IN with active current limitation |
| Electric connection type | Plug-in connection |
| Capacitive load | Up to 20,000 µF |
Technical Data - Mechanical
| Mounting method | Snap-fit on DIN rail (EN 60715) |
| Degree of protection | IP20 |
| Number of channels | 1 |
| Number of contacts (change-over contacts) | 0 |
| Number of contacts (normally closed contacts) | 0 |
| Number of contacts (normally open contacts) | 1 |
| Busbar type | LINE (+) and GND (-); max 60A in various lengths of up to 1m |
| Output terminals | 3x LOAD (+) and 3x GND (-) |
| Terminal type | Push in terminals |
| Terminal capacity | 2.5 mm² (flexible with ferrules) 4 mm² (rigid) |
Design verification as per IEC/EN 61439 - technical data
| Rated operational current for specified heat dissipation (In) | 16 A |
| Equipment heat dissipation, current-dependent | 2.9 W |
| Ambient operating temperature details | -30° C - 55° C |
| Permitted storage and transport temperature - min | -40 °C |
| Permitted storage and transport temperature - max | 100 °C |
Design verification as per IEC/EN 61439
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Additional information
| Features | Green = OK; Red = Triggered OFF = Channel not in operation Two-colored |
| Functions | DC-voltage over current |
| Protection | Electronic |
| Special features |
|
| Text field type | 17.5 mm x 6 mm |