View larger
PXS24S-e16/F/ORT
PXS24S16A002
PXS24S16A002
EATON - MOELLER
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Product Name | Eaton Moeller series xEffect - PXS24 current monitoring relay |
| Catalog Number | PXS24S16A002 |
| Model Code | PXS24S-e16/F/ORT |
| EAN | 9010238011281 |
| UPC | 786689167592 |
| Product Length/Depth | 127 mm |
| Product Height | 93 mm |
| Product Width | 18 mm |
| Product Weight | 0.118 kg |
| Compliances | CE UL508 RoHS conform |
| Certifications | EN45545-2 IEC 61373 |
| Type | Automation engineering 24V |
| Amperage Rating | 16 A |
| Voltage type | DC |
| Voltage rating | 24 VDC (15 VDC - 30 VDC) |
| Rated control supply voltage (Us) at AC, 50 Hz - min | 0 V |
| Rated control supply voltage (Us) at AC, 50 Hz - max | 0 V |
| Rated control supply voltage (Us) at AC, 60 Hz - min | 0 V |
| Rated control supply voltage (Us) at AC, 60 Hz - max | 0 V |
| Rated control supply voltage (Us) at DC - min | 15 V |
| Rated control supply voltage (Us) at DC - max | 30 V |
| Rated operational current (Ie) fix | 16 A |
| Current measurement - min | 0 A |
| Current measurement - max | 20.8 A |
| Overload current and short-circuit current trip | Type 1.3 x IN with active current limitation |
| Electric connection type | Plug-in connection |
| Capacitive load | Up to 20,000 µF |
| Mounting method | Snap-fit on DIN rail (EN 60715) |
| Degree of protection | IP20 |
| Number of channels | 1 |
| Number of contacts (change-over contacts) | 0 |
| Number of contacts (normally closed contacts) | 0 |
| Number of contacts (normally open contacts) | 1 |
| Busbar type | LINE (+) and GND (-); max 60A in various lengths of up to 1m |
| Output terminals | 3x LOAD (+) and 3x GND (-) |
| Terminal type | Push in terminals |
| Terminal capacity | 2.5 mm² (flexible with ferrules) 4 mm² (rigid) |
| Rated operational current for specified heat dissipation (In) | 16 A |
| Equipment heat dissipation, current-dependent | 2.9 W |
| Ambient operating temperature details | -30° C - 55° C |
| Permitted storage and transport temperature - min | -40 °C |
| Permitted storage and transport temperature - max | 100 °C |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
| Features | Green = OK; Red = Triggered OFF = Channel not in operation Two-colored |
| Functions | DC-voltage over current |
| Protection | Electronic |
| Special features |
|
| Text field type | 17.5 mm x 6 mm |
| Feature Name | Feature Value |
|---|---|
| Type of electric connection (EF003961) | Plug-in connection |
| With detachable clamps (EF003340) | No |
| External power supply required (EF003292) | No |
| Current measuring range (EF000417) | 0 A |
| Single-phase under current possible (EF003405) | No |
| Three-phase under current possible (EF003406) | No |
| Single-phase overcurrent possible (EF003407) | No |
| Three-phase overcurrent possible (EF003408) | No |
| Single-phase hysteresis possible (EF003394) | No |
| Three-phase hysteresis possible (EF003395) | No |
| Contains function DC-voltage under current (EF003409) | No |
| Contains function DC-voltage overcurrent (EF003410) | Yes |
| Function DC-current hysteresis (EF003411) | No |
| Min. adjustable delay-on energization time (EF008190) | 0 s |
| Max. permitted delay-on energization time (EF008189) | 0 s |
| Min. adjustable off-delay time (EF008192) | 0 s |
| Max. permitted off-delay time (EF008191) | 0 s |
| External current transformer (EF001923) | No |
| Number of contacts as normally closed contact (EF008255) | 0 |
| Number of contacts as normally open contact (EF008256) | 1 |
| Number of contacts as change-over contact (EF008257) | 0 |
| Width (EF000008) | 18 mm |
| Height (EF000040) | 93 mm |
| Depth (EF000049) | 127 mm |