EATON - MOELLER AING4 AING4 269516 Y7-269516 EATON ELECTRIC Power supply unit, 1p, 100VA, prim 230VAC, sec. 24VAC, 24 V DC, 10 V DC View larger
Images are for illustrative purposes only. Please refer to data sheet for details

AING4 269516 Y7-269516 EATON ELECTRIC Power supply unit, 1p, 100VA, prim 230VAC, sec. 24VAC, 24 V DC, 10 V DC

AING4

269516

Y7-269516

EATON - MOELLER

1 Pcs.

Power supply unit, 1p, 100VA, prim 230VAC, sec. 24VAC, 24 V DC, 10 V DC AING4 Eaton Moeller® series AING Power supply unit, 1p, 100VA, prim 230VAC, sec. 24VAC, 24 V DC, 10 V DC Universal power supply unit single-phase, safety transformer to IEC/EN 61558-2-2, 2-6, VDE 0570 Part 2-2, 2-6. rated power 100VA, one fuse per output voltage, a changeover contact for monitoring and annunciation, rated input voltage 230V +- 5%, rated output voltage / current: 24V AC / 4.2A, 10V DC / 1A, 24V DC / 3A

Automation > PLC system power supply
Transformers

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton Moeller® series AING Power supply unit
Catalog Number
269516
Model Code
AING4
EAN
4015082695163
Product Length/Depth
90 mm
Product Height
155 mm
Product Width
110 mm
Product Weight
3.1 kg
Certifications
VDE 0570 Part 2-2/2-6 (safety transformer)
IEC/EN 60204-1
VDE 0113
Safety transformer to IEC/EN 61558-2-2/2-6
Catalog Notes
Non-standard voltages on request

Features & Functions

Features
Fully Vacuum-impregnated
Separate windings
Reinforced insulation

General

Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
40 °C
Connection type
Terminations
Degree of Protection
IP20
Degree of Protection
IP20
Duty factor
100 %
Insulation class
B
Primary tapping
± 5 %
Product category
Universal power supply unit AING
Suitable for
Safety functions
Type
Single-phase power supply

Electrical rating

Input current at AC - max
0.44 A
Input voltage at AC 50 Hz - min
230 V
Input voltage at AC 50 Hz - max
230 V
Input voltage at DC - min
0 V
Input voltage at DC - max
0 V
Output current at AC, 50 Hz - max
4.2 A
Output voltage at AC 50 Hz - max
24 V
Output voltage at DC - min
24 V
Output voltage at DC - max
24 V
Rated frequency - min
50 Hz
Rated frequency - max
60 Hz
Rated power
0.1 VA

Design verification

Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
50 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

ETIM for 269516 PLC's (EC000599)
Feature Name Feature Value
Input voltage AC 50 Hz (EF007118) 230 V
Input voltage AC 60 Hz (EF007119) 230 V
Input voltage DC (EF007120) 0 V
Type of voltage (input voltage) (EF003033) AC/DC
Max. input current AC 50 Hz (EF007360) 0.44 A
Max. input current AC 60 Hz (EF007361) 0.44 A
Max. input current DC (EF007362) 0 A
Type of output voltage (EF008222) AC/DC
Output voltage AC 50 Hz (EF006999) 24 V
Output voltage AC 60 Hz (EF007000) 24 V
Output voltage DC (EF007001) 24 V
Max. output current AC 50 Hz (EF007351) 4.2 A
Max. output current AC 60 Hz (EF007352) 4.2 A
Max. output current DC (EF007353) 3 A
Power output (EF003034) 100 W
Redundancy (EF003156) No
Suitable for safety functions (EF001597) Yes
Width (EF000008) 110 mm
Height (EF000040) 155 mm
Depth (EF000049) 90 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.