View larger
M22-R4K7 229490 Y7-229490 EATON ELECTRIC Potentiometer, 4, 7k, front mount
M22-R4K7
229490
Y7-229490
EATON - MOELLER
1 Pcs.
Automation > Potentiometer for command devices
Auxiliary Control and Signalling Elements
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller model M22-R4K7 is a front-mounted potentiometer engineered for manual process control tasks in industrial control environments. Operators use panel-mounted variable resistors of this type to continuously adjust parameters such as motor speeds, temperature setpoints, and valve positions in automated machinery.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Name: Eaton Moeller® series M22 Potentiometer
- Catalog Number: 229490
- Model Code: M22-R4K7
- EAN: 4015082294908
- Product Length/Depth: 70 mm
- Product Height: 29 mm
- Product Width: 29 mm
- Product Weight: 0.034 kg
- Compliances: CE Marked
- Bezel color: Titanium
- Design: Classical
- Electric connection type: Screw connection
- Fitted with:: 3 individual screw terminals
- Accuracy: ± 10 % (linear), Resistance value
- Degree of protection: IP66 NEMA Other
- Lifespan, mechanical: 25,000 Operations
More info
▲General specifications
| Product Name | Eaton Moeller® series M22 Potentiometer |
| Catalog Number | 229490 |
| Model Code | M22-R4K7 |
| EAN | 4015082294908 |
| Product Length/Depth | 70 mm |
| Product Height | 29 mm |
| Product Width | 29 mm |
| Product Weight | 0.034 kg |
| Compliances | CE Marked |
| Certifications | UL 508 EN 60947-5 IEC 60947-5 CSA Std. C22.2 No. 94-91 CSA Std. C22.2 No. 14-05 CSA Class No.: 3211-03 IEC/EN 60947-5 CSA IEC/EN 60947 CSA-C22.2 No. 94-91 CSA-C22.2 No. 14-05 CE UL Category Control No.: NKCR CSA File No.: 012528 UL File No.: E29184 VDE 0660 UL |
Features & Functions
| Bezel color | Titanium |
| Design | Classical |
| Electric connection type | Screw connection |
| Fitted with: | 3 individual screw terminals |
General information
| Accuracy | ± 10 % (linear), Resistance value |
| Degree of protection | IP66 NEMA Other |
| Lifespan, mechanical | 25,000 Operations |
| Opening diameter | 22.5 mm |
| Overvoltage category | III |
| Pollution degree | 3 |
| Rated impulse withstand voltage (Uimp) | 4000 V AC |
| Type | Potentiometer |
Ambient conditions, mechanical
| Mounting position | As required |
| Shock resistance | 30 g, Mechanical, According to IEC/EN 60068-2-27, Sinusoidal shock 11 ms Mechanical, According to IEC/EN 60068-2-27 |
Climatic environmental conditions
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature - max | 70 °C |
| Climatic proofing | Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
Terminal capacities
| Terminal capacity (solid) | 0.5 - 1.5 mm² |
| Terminal capacity (stranded) | 0.5 - 1.5 mm² |
| Tightening torque | 0.5 Nm, Screw terminals |
Electrical rating
| Power consumption | 0.5 W |
| Rated insulation voltage (Ui) | 250 V |
| Rated power | 0.5 VA |
| Resistance | 4700 Ohm |
Communication
| Connection to SmartWire-DT | No |
Design verification
| Equipment heat dissipation, current-dependent Pvid | 0 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 0 W |
| Rated operational current for specified heat dissipation (In) | 0 A |
| Static heat dissipation, non-current-dependent Pvs | 0.5 W |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Please enquire |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |