View larger
PLN6-C16/1N-DE 263282 Y7-263282 EATON ELECTRIC Miniature circuit breaker (MCB), 16A, 1pole+N, type C charact..
PLN6-C16/1N-DE
PLN6-C16/1N-DE
Y7-263282
EATON - MOELLER
1 unit
Automation > Miniature circuit breaker (MCB)
Modular Switchgear - Tertiary
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The PLN6-C16/1N-DE 263282 Y7-263282 EATON ELECTRIC Miniature circuit breaker (MCB), 16A, 1pole+N, type C charact.. serves as a miniature circuit breaker designed to interrupt electrical circuits during overloads and short circuits, ensuring system protection. Units of this configuration are widely deployed in residential and commercial distribution enclosures. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Built-in depth: 70.5 mm
- Release characteristic: C
- Number of poles (total): 2
- Number of protected poles: 1
- Rated current: 16 A
- Rated voltage: 230 V
- Rated insulation voltage Ui: 440 V
- Rated impulse withstand voltage Uimp: 4 kV
- Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V: 6 kA
- Voltage type: AC
- Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V: 6 kA
- Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V: 0 kA
- Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V: 0 kA
- Frequency: 50 Hz
- Power loss: 3 W
- Current limiting class: 3
More info
▲General specifications
| Product Name | Eaton Moeller series xPole - PLN6 MCB |
| Catalog Number | 263282 |
| Model Code | PLN6-C16/1N-DE |
| EAN | 4015082632823 |
| Product Length/Depth | 71 mm |
| Product Height | 82 mm |
| Product Width | 17.6 mm |
| Product Weight | 0.13 kg |
| Compliances | RoHS conform |
Delivery program
| Number of poles (total) | 2 |
| Number of poles (protected) | 1 |
| Release characteristic | C |
| Amperage Rating | 16 A |
Technical Data - Electrical
| Voltage type | AC |
| Rated operational voltage (Ue) - max | 230 V |
| Rated insulation voltage (Ui) | 440 V |
| Rated impulse withstand voltage (Uimp) | 4 kV |
| Frequency rating - min | 50 Hz |
| Frequency rating - max | 60 Hz |
| Overvoltage category | III |
| Pollution degree | 2 |
Technical Data - Mechanical
| Width in number of modular spacings | 1 |
| Built-in depth | 70.5 mm |
| Degree of protection | IP20 |
| Connectable conductor cross section (solid-core) - min | 1 mm² |
| Connectable conductor cross section (solid-core) - max | 16 mm² |
| Connectable conductor cross section (multi-wired) - min | 1 mm² |
| Connectable conductor cross section (multi-wired) - max | 16 mm² |
Design verification as per IEC/EN 61439 - technical data
| Rated operational current for specified heat dissipation (In) | 16 A |
| Heat dissipation per pole, current-dependent | 0 W |
| Equipment heat dissipation, current-dependent | 2.8 W |
| Static heat dissipation, non-current-dependent | 0 W |
| Heat dissipation capacity | 0 W |
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature - max | 75 °C |
Design verification as per IEC/EN 61439
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Additional information
| Current limiting class | 3 |
| Features | Concurrently switching N-neutral Additional equipment possible |
| Special features | Ambient temperature hint: Starting at 55 °C a 1 °C increase results in a 0.5% linear reduction of current carrying capacity |